Short answer

Efficiency is about 93.09%. To make regulation zero, the net power factor must be around 0.894 leading, requiring a shunt capacitor of approximately 8 MVAr at the receiving end.

A 3-phase 50 Hz line operating at 33 kV is supplying a load of 20 MW at 0.995 p.f. leading. The series impedance of the line is 4 + j8 Ω/ph. Determine the power transmission efficiency of the line. How can the line voltage regulation be made zero?

Short line, Z=4+j8 ΩZ = 4 + j8\ \Omega/phase, VR=33V_R = 33 kV, load 20 MW at 0.995 pf leading.

Efficiency

I=20×1063×33 000×0.995=351.67 APloss=3I2R=3(351.67)2(4)=1.484 MWη=2020+1.484×100=93.09%\begin{aligned} I &= \frac{20\times10^6}{\sqrt3\times33\,000\times0.995} = 351.67\ \text{A} \\ P_{loss} &= 3I^2R = 3(351.67)^2(4) = 1.484\ \text{MW} \\ \eta &= \frac{20}{20 + 1.484}\times100 = 93.09\% \end{aligned}

Present regulation (for reference): ϕ=5.73∘\phi = 5.73^\circ leading,

VS=19 052.6+351.67∠5.73∘ (4+j8)=20 384.3∠8.29∘ VV_S = 19\,052.6 + 351.67\angle5.73^\circ\,(4 + j8) = 20\,384.3\angle8.29^\circ\ \text{V}

i.e. 35.31 kV line, regulation =6.99%= 6.99\%. It is still positive because the pf is only slightly leading.

Making regulation zero

For a short line,

%VR≈I(Rcos⁡ϕ−Xsin⁡ϕ)VR×100(leading pf)\%VR \approx \frac{I(R\cos\phi - X\sin\phi)}{V_R}\times 100 \quad (\text{leading pf})

This is zero when

tan⁡ϕ=RX=48=0.5⇒cos⁡ϕ=0.894 leading\tan\phi = \frac{R}{X} = \frac{4}{8} = 0.5 \Rightarrow \cos\phi = 0.894\ \text{leading}

So regulation is made zero by making the load (or load plus compensator) take more leading current:

  • Connect a shunt capacitor bank / synchronous condenser at the receiving end.
  • Required net leading reactive power: Q=Ptan⁡ϕ=20×0.5=10Q = P\tan\phi = 20\times0.5 = 10 MVAr.
  • The load already supplies 20tan⁡(5.73∘)=2.0120\tan(5.73^\circ) = 2.01 MVAr leading, so the capacitor needed is
QC=10−2.01=7.99 MVArQ_C = 10 - 2.01 = 7.99\ \text{MVAr} Cph=QCωVL2=7.99×106314.16×33 0002=23.36 μF (star)C_{ph} = \frac{Q_C}{\omega V_L^2} = \frac{7.99\times10^6}{314.16\times33\,000^2} = 23.36\ \mu\text{F (star)}

(An exact solution of ∣VS∣=∣VR∣|V_S| = |V_R| gives net pf 0.847 leading and QCQ_C ≈ 10.55 MVAr.)

Answer: Efficiency ≈ 93.09 %. Zero regulation needs a net pf of about 0.894 leading, i.e. a shunt capacitor of about 8 MVAr at the receiving end.