- Asked 2/23
- 2071 Bhadra · 6 marks
Zero regulation for 40 MW leading load
Short answer
The present regulation is −0.78%. To make it zero, absorb approximately 3.93 MVAr using a shunt reactor at the receiving end, bringing the net power factor to about 0.933 leading.
A 50 Hz, 3-phase, 132 kV overhead line is supplying a load of 40 MW at 0.9 p.f. leading. The line has series impedance of 12 + j36 Ω/phase. How can the voltage regulation of the line be made zero?
Short line: , = 132 kV, load 40 MW at 0.9 pf leading.
Present regulation
The regulation is negative: the load is too leading, so the receiving-end voltage is higher than the sending-end voltage.
Condition for zero regulation
Approximate condition: , i.e. , giving pf leading.
Exact condition kV with = 40 MW (line kV, MW, MVAr):
Taking the root nearer zero:
How to make it zero
The load now supplies MVAr (leading). The leading VAr must be reduced to 15.44 MVAr, so connect a shunt reactor at the receiving end of
(Alternatively, reduce the excitation of a synchronous load/condenser so that it draws less leading current.)
Answer: Regulation is now −0.78 %. It is made zero by absorbing ≈ 3.9 MVAr with a shunt reactor at the receiving end, bringing the net pf to ≈ 0.933 leading.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 33 kV, 12 MW leading load: efficiency, zero regulation · Power System Analysis I, chapter 6 · asked 2×
- Efficiency at 0.995 leading pf and zero regulation · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- 33 kV, 15 MW line: efficiency and regulation · Power System Analysis I, chapter 6
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×