Regulation and efficiency of 100 km, 110 kV line
Short answer
Using nominal-T model for this 100 km line, total series impedance Z = 15.3 + j38.01 Ω, shunt admittance Y = 3.01×10⁻⁴ S. Sending voltage found 115.62 kV, giving voltage regulation 5.72 %. Total losses 0.585 MW, efficiency 97.16 %.
A 3-phase, 50 Hz, 100 km long overhead line has the following line constants: resistance per phase per km = 0.153 Ω, inductance per phase per km = 1.21 mH, capacitance per phase per km = 0.00958 μF. The line supplies a load of 20 MW at 0.9 power factor lagging at a line voltage of 110 kV at the receiving end. Calculate the regulation and efficiency.
A 100 km line is a medium line, so it is solved here with the nominal-T model: total series impedance split into two halves, with the total shunt admittance at the middle.
Line constants (per phase, total)
Receiving-end quantities
Nominal-T solution
Sending-end line voltage kV.
Regulation
At no load the receiving voltage is , with :
(If the no-load Ferranti rise is ignored, .)
Efficiency
Answer: Voltage regulation ≈ 5.72 % (sending end 115.62 kV), efficiency ≈ 97.16 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 12 km line at 32.5 kV: regulation and capacitor · Power System Analysis I, chapter 6
- Short line 40 km, 381 MVA: regulation and efficiency · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- 220 kV double circuit efficiency and regulation · Transmission and Distribution System Design, chapter 4
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×