Regulation and efficiency of 100 km, 110 kV line

Short answer

Using nominal-T model for this 100 km line, total series impedance Z = 15.3 + j38.01 Ω, shunt admittance Y = 3.01×10⁻⁴ S. Sending voltage found 115.62 kV, giving voltage regulation 5.72 %. Total losses 0.585 MW, efficiency 97.16 %.

A 3-phase, 50 Hz, 100 km long overhead line has the following line constants: resistance per phase per km = 0.153 Ω, inductance per phase per km = 1.21 mH, capacitance per phase per km = 0.00958 μF. The line supplies a load of 20 MW at 0.9 power factor lagging at a line voltage of 110 kV at the receiving end. Calculate the regulation and efficiency.

A 100 km line is a medium line, so it is solved here with the nominal-T model: total series impedance split into two halves, with the total shunt admittance at the middle.

Line constants (per phase, total)

R=0.153×100=15.3 ΩXL=2π(50)(1.21×10−3)(100)=38.01 ΩY=2π(50)(0.00958×10−6)(100)=3.010×10−4 SZ/2=7.65+j19.01 Ω\begin{aligned} R &= 0.153 \times 100 = 15.3\ \Omega \\ X_L &= 2\pi (50)(1.21\times10^{-3})(100) = 38.01\ \Omega \\ Y &= 2\pi (50)(0.00958\times10^{-6})(100) = 3.010\times10^{-4}\ \text{S} \\ Z/2 &= 7.65 + j19.01\ \Omega \end{aligned}

Receiving-end quantities

VR=110 0003=63 508.5∠0∘ VIR=20×1063×63 508.5×0.9=116.64∠−25.84∘ A\begin{aligned} V_R &= \frac{110\,000}{\sqrt3} = 63\,508.5\angle 0^\circ\ \text{V} \\ I_R &= \frac{20\times10^6}{3 \times 63\,508.5 \times 0.9} = 116.64\angle -25.84^\circ\ \text{A} \end{aligned}

Nominal-T solution

V1=VR+IRZ2=65 297.6∠1.41∘ VIC=jYV1=19.65∠91.41∘ AIS=IR+IC=109.05∠−16.62∘ AVS=V1+ISZ2=66 754.4∠2.88∘ V\begin{aligned} V_1 &= V_R + I_R \frac{Z}{2} = 65\,297.6\angle 1.41^\circ\ \text{V} \\ I_C &= jY V_1 = 19.65\angle 91.41^\circ\ \text{A} \\ I_S &= I_R + I_C = 109.05\angle -16.62^\circ\ \text{A} \\ V_S &= V_1 + I_S \frac{Z}{2} = 66\,754.4\angle 2.88^\circ\ \text{V} \end{aligned}

Sending-end line voltage =3×66.754=115.62= \sqrt3 \times 66.754 = 115.62 kV.

Regulation

At no load the receiving voltage is VS/∣A∣V_S/|A|, with A=1+YZ2=0.9943∠0.13∘A = 1 + \frac{YZ}{2} = 0.9943\angle 0.13^\circ:

VR0=66 754.40.9943=67 138.3 V%VR=67 138.3−63 508.563 508.5×100=5.72%\begin{aligned} V_{R0} &= \frac{66\,754.4}{0.9943} = 67\,138.3\ \text{V} \\ \%VR &= \frac{67\,138.3 - 63\,508.5}{63\,508.5}\times 100 = 5.72\% \end{aligned}

(If the no-load Ferranti rise is ignored, (VS−VR)/VR=5.11%(V_S - V_R)/V_R = 5.11\%.)

Efficiency

Ploss=3(∣IR∣2+∣IS∣2)R2=3 (116.642+109.052)(7.65)=0.585 MWη=2020+0.585×100=97.16%\begin{aligned} P_{loss} &= 3\left(|I_R|^2 + |I_S|^2\right)\frac{R}{2} \\ &= 3\,(116.64^2 + 109.05^2)(7.65) = 0.585\ \text{MW} \\ \eta &= \frac{20}{20 + 0.585}\times 100 = 97.16\% \end{aligned}

Answer: Voltage regulation ≈ 5.72 % (sending end 115.62 kV), efficiency ≈ 97.16 %.