- 2075 Baisakh · 6 marks
Short line 40 km, 381 MVA: regulation and efficiency
Short answer
Sending end line voltage is 246.2 kV, three-phase power 322.8 MW + j278.6 MVAr. Voltage regulation is 11.91% and efficiency 94.43%, based on short-line model with Z=6+j16.667 Ω.
A 220 kV, three phase transmission line is 40 km long. The resistance per phase is 0.15 Ω per km and the inductance per phase is 1.3263 mH per km. The shunt capacitance is negligible. Use the short line model to find the voltage and power at the sending end and the voltage regulation and efficiency when the line is supplying a three phase load of 381 MVA at 0.8 power factor lagging at 220 kV.
Short-line model: shunt capacitance neglected, .
Line impedance
Receiving end
Sending-end voltage
Line value kV.
Sending-end power
Sending-end pf lagging.
Regulation
Efficiency
Receiving power MW.
(Check: loss MW.)
Answer: = 246.2 kV (line), = 322.8 MW + j278.6 MVAr, regulation 11.91 %, efficiency 94.43 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 220 kV double circuit efficiency and regulation · Transmission and Distribution System Design, chapter 4
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Restriking voltage numerical (6.6 kV, 8 mH) · Switchgear and Protection, chapter 6 · asked 2×
- Restriking voltage numerical (11 kV, 10 mH) · Switchgear and Protection, chapter 6 · asked 2×