Short answer

Sending end line voltage is 246.2 kV, three-phase power 322.8 MW + j278.6 MVAr. Voltage regulation is 11.91% and efficiency 94.43%, based on short-line model with Z=6+j16.667 Ω.

A 220 kV, three phase transmission line is 40 km long. The resistance per phase is 0.15 Ω per km and the inductance per phase is 1.3263 mH per km. The shunt capacitance is negligible. Use the short line model to find the voltage and power at the sending end and the voltage regulation and efficiency when the line is supplying a three phase load of 381 MVA at 0.8 power factor lagging at 220 kV.

Short-line model: shunt capacitance neglected, IS=IRI_S = I_R.

Line impedance

R=0.15×40=6 ΩX=2π(50)(1.3263×10−3)(40)=16.667 ΩZ=6+j16.667 Ω\begin{aligned} R &= 0.15\times40 = 6\ \Omega \\ X &= 2\pi(50)(1.3263\times10^{-3})(40) = 16.667\ \Omega \\ Z &= 6 + j16.667\ \Omega \end{aligned}

Receiving end

VR=2203=127.02∠0∘ kVIR=381×1063×220×103=999.87∠−36.87∘ A\begin{aligned} V_R &= \frac{220}{\sqrt3} = 127.02\angle0^\circ\ \text{kV} \\ I_R &= \frac{381\times10^6}{\sqrt3\times220\times10^3} = 999.87\angle-36.87^\circ\ \text{A} \end{aligned}

Sending-end voltage

VS=VR+IRZ=127.02+(0.99987∠−36.87∘)(17.71∠70.20∘)=127.02+17.71∠33.33∘=142.15∠3.93∘ kV (phase)\begin{aligned} V_S &= V_R + I_R Z = 127.02 + (0.99987\angle-36.87^\circ)(17.71\angle70.20^\circ) \\ &= 127.02 + 17.71\angle33.33^\circ \\ &= 142.15\angle3.93^\circ\ \text{kV (phase)} \end{aligned}

Line value =3×142.15=246.21= \sqrt3\times142.15 = 246.21 kV.

Sending-end power

SS=3VSIS∗=3(142.15∠3.93∘)(0.99987∠36.87∘)=322.80+j278.59 MVA\begin{aligned} S_S &= 3V_S I_S^* = 3(142.15\angle3.93^\circ)(0.99987\angle36.87^\circ) \\ &= 322.80 + j278.59\ \text{MVA} \end{aligned}

Sending-end pf =cos⁡(40.80∘)=0.757= \cos(40.80^\circ) = 0.757 lagging.

Regulation

%VR=246.21−220220×100=11.91%\%VR = \frac{246.21 - 220}{220}\times100 = 11.91\%

Efficiency

Receiving power PR=381×0.8=304.8P_R = 381\times0.8 = 304.8 MW.

η=304.8322.80×100=94.43%\eta = \frac{304.8}{322.80}\times100 = 94.43\%

(Check: loss =3I2R=3(999.87)2(6)=18.0= 3I^2R = 3(999.87)^2(6) = 18.0 MW.)

Answer: VSV_S = 246.2 kV (line), SSS_S = 322.8 MW + j278.6 MVAr, regulation 11.91 %, efficiency 94.43 %.