- 2081 Chaitra (new course) · 3+3 marks
Regulation and zero-regulation power factor of 100 kVA transformer
Short answer
Use percent regulation = epsilon_r cos phi + epsilon_x sin phi with epsilon_x = sqrt(10^2 - 5^2) = 8.66%. At 0.8 lagging regulation is 9.20%; zero regulation occurs at 0.866 leading pf.
A single phase, 100 kVA, 2000/200 V, 50 Hz transformer has an impedance drop of 10% and resistance drop of 5%. Calculate: a) The regulation at full load 0.8 power factor lagging. b) The value of power factor at which regulation is zero.
Per-unit resistance and impedance drops are given: , , so the reactance drop is
a) Regulation at full load, 0.8 pf lagging
b) Power factor for zero regulation
Regulation is zero for a leading pf, when
Answer: (a) regulation = 9.20%; (b) zero regulation at pf = 0.866 leading.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit, efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Efficiency and regulation of 5 kVA transformer · Electrical Machines I, chapter 2
- Voltage regulation of transformer for lagging load · Electrical Machines I, chapter 2
- Efficiency of 5 kVA transformer at 2 kW load · Electrical Machines I, chapter 2
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1