- 2075 Chaitra · 8 marks
Power angle and regulation of 10 kVA alternator
Short answer
Vph=230.94 V, I=14.43 A. Using E=√((Vcosφ+IRa)²+(Vsinφ+IXs)²) at 0.8 pf lagging gives E=341.9 V/phase. Power angle δ=θ−φ=18.97°. Voltage regulation = (341.9−230.94)/230.94×100 = 48.04%.
A 3-phase, 10 kVA, 400 V, 50 Hz star-connected synchronous alternator supplies the rated load at 0.8 power factor lagging. If the armature resistance is 0.5 Ω and synchronous reactance is 10 Ω, find the power angle and voltage regulation.
Given: star, 10 kVA, 400 V, 50 Hz, , ; rated load at 0.8 pf lagging.
Phase voltage and current
Excitation emf
Power angle
The angle of from the current phasor is
E = 341.9 V
/
/ delta = 18.97 deg
O-------------- V = 230.9 V
\ phi = 36.87 deg
\ I = 14.43 A
Voltage regulation
(The regulation is high because is large compared with the rated impedance , i.e. pu.)
Answer: power angle δ = 18.97°, voltage regulation = 48.04% (E = 341.9 V per phase).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Regulation and power angle of 1650 kVA generator · Electric Machines II, chapter 1
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×