1600 kVA alternator: emf, regulation, power angle

Short answer

Using Vph=7794.2 V, Ra=1.5 Ω, Xs=30 Ω: (i) 0.8 lagging, I=68.43 A, E_line=16011 V, regulation 18.60%, δ=9.85°; (ii) unity pf, I=54.74 A, E_line=13936 V, regulation 3.23%, δ=11.78°. Calculated via phasor addition.

A 3 phase star connected alternator is rated at 1600 kVA, 13.5 kV having per phase armature effective resistance and synchronous reactance of 1.5 Ω1.5\ \Omega and 30 Ω30\ \Omega respectively. Calculate the line value of emf generated, voltage regulation and power angle for a load of 1.28 MW at, i) 0.8 pf lagging ii) unity power factor.

Given: 1600 kVA, 13.5 kV, star, Ra=1.5 ΩR_a = 1.5\ \Omega, Xs=30 ΩX_s = 30\ \Omega per phase. Load P=1.28P = 1.28 MW at rated voltage.

Vph=135003=7794.2 V,I=1.28×1063×13500×cos⁡ϕV_{ph} = \frac{13500}{\sqrt3} = 7794.2\ \text{V}, \qquad I = \frac{1.28\times10^6}{\sqrt3\times13500\times\cos\phi} E⃗=V⃗+I⃗(Ra+jXs),Regulation=E−VV×100\vec E = \vec V + \vec I(R_a + jX_s), \qquad \text{Regulation} = \frac{E - V}{V}\times100

(i) 0.8 pf lagging

I=1.28×1063×13500×0.8=68.43 AI = \frac{1.28\times10^6}{\sqrt3\times13500\times0.8} = 68.43\ \text{A} IRa=102.64 V,IXs=2052.80 VIR_a = 102.64\ \text{V}, \quad IX_s = 2052.80\ \text{V} E=(7794.2+102.64×0.8+2052.80×0.6)2+(2052.80×0.8−102.64×0.6)2E = \sqrt{(7794.2 + 102.64\times0.8 + 2052.80\times0.6)^2 + (2052.80\times0.8 - 102.64\times0.6)^2} Eph=9244.2 V,EL=16011 VE_{ph} = 9244.2\ \text{V}, \qquad E_L = 16011\ \text{V} Regulation=9244.2−7794.27794.2×100=18.60%\text{Regulation} = \frac{9244.2 - 7794.2}{7794.2}\times100 = 18.60\% δ=tan⁡−11642.2−61.67794.2+82.1+1231.7≈9.85∘\delta = \tan^{-1}\frac{1642.2-61.6}{7794.2 + 82.1 + 1231.7}\approx 9.85^\circ

(ii) Unity pf

I=1.28×1063×13500=54.74 A,IRa=82.11 V,IXs=1642.24 VI = \frac{1.28\times10^6}{\sqrt3\times13500} = 54.74\ \text{A}, \quad IR_a = 82.11\ \text{V}, \quad IX_s = 1642.24\ \text{V} E=(7794.2+82.11)2+1642.242E = \sqrt{(7794.2 + 82.11)^2 + 1642.24^2} Eph=8045.7 V,EL=13935.6 VE_{ph} = 8045.7\ \text{V}, \qquad E_L = 13935.6\ \text{V} Regulation=8045.7−7794.27794.2×100=3.23%,δ=tan⁡−11642.247876.3=11.78∘\text{Regulation} = \frac{8045.7-7794.2}{7794.2}\times100 = 3.23\%, \qquad \delta = \tan^{-1}\frac{1642.24}{7876.3} = 11.78^\circ
CaseII (A)ELE_L (V)RegulationPower angle δ\delta
0.8 lagging68.431601118.60 %9.85°
Unity54.74139363.23 %11.78°

Answer: as in the table (emf is line value; power angle is the angle between EE and VV).