- 2079 Jestha · 8 marks
1500 kVA alternator: excitation emf, voltage at leading pf
Short answer
For 0.8 lagging, per-phase Vph=3810.5 V, I=131.22 A, E_ph=4366 V (line 7562 V) from phasor sum. For 0.8 leading with same E and I, solving V²+2V·789.1·cos123.06°+789.1²=4366² gives terminal Vph=4746 V (line 8220 V).
A 1500 kVA, 6600 V, 3 phase star connected alternator with a resistance of and reactance of per phase delivers full load current at a power factor of 0.8 lagging and at normal rated voltage. Calculate the (i) excitation EMF (ii) terminal voltage for same excitation and the load current at 0.8 power factor leading.
Given: 1500 kVA, 6600 V, star, , per phase, full-load at 0.8 pf lagging, rated voltage.
(i) Excitation emf (0.8 lagging)
Taking as reference, , :
(ii) Terminal voltage at 0.8 leading (same and )
. The drop has magnitude V at from . With :
Solving this quadratic gives (taking the positive root)
Answer: (i) V (line 7562 V); (ii) terminal voltage V line (4746 V per phase). The voltage rises because the leading current's armature reaction is magnetising.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Synchronous motor: pf when input rises to 1500 kW · Electrical Machines, chapter 6
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- Sync generator (6600 V) leading voltage · Electrical Machine, chapter 6 · asked 2×
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×