Emf and regulation of 1500 kVA alternator
Short answer
Using per-phase voltage 6928 V and current 80.2 A. At 0.75 leading pf: generated emf = 5945 V/phase (10.30 kV line), regulation = –14.2%. At 0.75 lagging pf: emf = 8490 V/phase (14.71 kV line), regulation = +22.6%. Calculated via E = √[(Vcosφ+IR_a)² + (Vsinφ ∓ IX_s)²].
A 3-phase star-connected alternator is rated at 1500 kVA, 12000 V. The armature effective resistance and synchronous reactance are 2 Ω and 25 Ω respectively per phase. Calculate the emf generated and percentage voltage regulation for a load of 1250 kW at power factors of: (i) 0.75 leading (ii) 0.75 lagging.
Given: star connected, = 12000 V, , per phase, load 1250 kW at 0.75 pf.
(Note: this load is kVA, which is above the 1500 kVA rating. The calculation follows the data given in the question.)
(i) 0.75 pf leading
(ii) 0.75 pf lagging
Answer: (i) 0.75 lead: E = 5944.6 V/phase (10.30 kV line), regulation = −14.20%; (ii) 0.75 lag: E = 8490.3 V/phase (14.71 kV line), regulation = +22.55%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Internal emf, no-load emf and regulation · Electric Machines II, chapter 1
- Emf, regulation and loading with given load impedance · Electric Machines II, chapter 1
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6