Short answer

Using per-phase voltage 6928 V and current 80.2 A. At 0.75 leading pf: generated emf = 5945 V/phase (10.30 kV line), regulation = –14.2%. At 0.75 lagging pf: emf = 8490 V/phase (14.71 kV line), regulation = +22.6%. Calculated via E = √[(Vcosφ+IR_a)² + (Vsinφ ∓ IX_s)²].

A 3-phase star-connected alternator is rated at 1500 kVA, 12000 V. The armature effective resistance and synchronous reactance are 2 Ω and 25 Ω respectively per phase. Calculate the emf generated and percentage voltage regulation for a load of 1250 kW at power factors of: (i) 0.75 leading (ii) 0.75 lagging.

Given: star connected, VLV_L = 12000 V, Ra=2 ΩR_a = 2\ \Omega, Xs=25 ΩX_s = 25\ \Omega per phase, load 1250 kW at 0.75 pf.

Vph=120003=6928.2 VI=1250×1033×12000×0.75=80.19 Acos⁡ϕ=0.75,sin⁡ϕ=0.6614Vcos⁡ϕ+IRa=5196.15+80.19×2=5356.53 VVsin⁡ϕ=4582.58 V,IXs=80.19×25=2004.69 V\begin{aligned} V_{ph} &= \frac{12000}{\sqrt3} = 6928.2\ \text{V} \\ I &= \frac{1250\times10^3}{\sqrt3\times12000\times0.75} = 80.19\ \text{A} \\ \cos\phi &= 0.75,\quad \sin\phi = 0.6614 \\ V\cos\phi + IR_a &= 5196.15 + 80.19\times2 = 5356.53\ \text{V} \\ V\sin\phi &= 4582.58\ \text{V},\quad IX_s = 80.19\times25 = 2004.69\ \text{V} \end{aligned}

(Note: this load is 1250/0.75=16671250/0.75 = 1667 kVA, which is above the 1500 kVA rating. The calculation follows the data given in the question.)

(i) 0.75 pf leading

E=(Vcos⁡ϕ+IRa)2+(Vsin⁡ϕ−IXs)2=5356.532+(4582.58−2004.69)2=5356.532+2577.892=5944.57 V per phaseEL=3×5944.57=10296 V%Reg=5944.57−6928.26928.2×100=−14.20%\begin{aligned} E &= \sqrt{(V\cos\phi + IR_a)^2 + (V\sin\phi - IX_s)^2} \\ &= \sqrt{5356.53^2 + (4582.58 - 2004.69)^2} \\ &= \sqrt{5356.53^2 + 2577.89^2} = 5944.57\ \text{V per phase} \\ E_L &= \sqrt3 \times 5944.57 = 10296\ \text{V} \\ \%\text{Reg} &= \frac{5944.57 - 6928.2}{6928.2}\times100 = -14.20\% \end{aligned}

(ii) 0.75 pf lagging

E=5356.532+(4582.58+2004.69)2=5356.532+6587.262=8490.26 V per phaseEL=3×8490.26=14706 V%Reg=8490.26−6928.26928.2×100=22.55%\begin{aligned} E &= \sqrt{5356.53^2 + (4582.58 + 2004.69)^2} \\ &= \sqrt{5356.53^2 + 6587.26^2} = 8490.26\ \text{V per phase} \\ E_L &= \sqrt3 \times 8490.26 = 14706\ \text{V} \\ \%\text{Reg} &= \frac{8490.26 - 6928.2}{6928.2}\times100 = 22.55\% \end{aligned}

Answer: (i) 0.75 lead: E = 5944.6 V/phase (10.30 kV line), regulation = −14.20%; (ii) 0.75 lag: E = 8490.3 V/phase (14.71 kV line), regulation = +22.55%.