- 2073 Shrawan · 7 marks
Emf, regulation and loading with given load impedance
Short answer
With load impedance 80+j60 Ω, generated emf is 6546.2 V per phase (11.34 kV line), regulation 3.08%. The generator supplies 1210 kVA, so it is under-loaded by 19.33%.
A 3-phase, star-connected 3-phase synchronous generator is rated as 1500 kVA, 11 kV. The armature winding resistance is 0.8 ohm per phase and synchronous reactance is 4 ohms per phase. If the generator is supplying power to a three phase balanced load of (80+j60) ohm per phase at rated terminal voltage, calculate emf generated and voltage regulation. Is the generator overloaded OR under-loaded? Calculate the percentage by which it is overloaded OR under-loaded.
Given: star, 1500 kVA, 11 kV, , ; load per phase at rated voltage.
Load current
EMF generated
Voltage regulation
Overloaded or under-loaded?
Answer: E = 6546.2 V/phase (11.34 kV line); regulation = 3.08%; the generator is under-loaded by 19.33% (supplies 1210 kVA, 968 kW).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×