Regulation of 10 kVA round-rotor generator
Short answer
At rated load: (a) 0.8 lagging, regulation = +21.8%; (b) 0.8 leading, regulation = –3.08%. Zero regulation occurs at a leading power factor of 0.869, obtained by solving E = V for φ.
A 3-phase, star-connected, round-rotor synchronous generator rated at 10 kVA, 230 V has an armature resistance of 0.5 ohm per phase and a synchronous reactance of 1.2 ohm per phase. Calculate the percentage voltage regulation at full load at power factors of (a) 0.8 lagging, (b) 0.8 leading, (c) determine the power factor such that the voltage regulation is zero on full load.
Given: star, 10 kVA, 230 V, , per phase.
(a) 0.8 pf lagging
(b) 0.8 pf leading
(c) Power factor for zero regulation
Zero regulation means . With and current ( positive for leading):
Answer: (a) 21.81%; (b) −3.08%; (c) zero regulation at pf = 0.869 leading.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Regulation and power angle of 1650 kVA generator · Electric Machines II, chapter 1
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Emf, regulation and loading with given load impedance · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- Sync generator (6600 V) leading voltage · Electrical Machine, chapter 6 · asked 2×