Short answer

At rated load: (a) 0.8 lagging, regulation = +21.8%; (b) 0.8 leading, regulation = –3.08%. Zero regulation occurs at a leading power factor of 0.869, obtained by solving E = V for φ.

A 3-phase, star-connected, round-rotor synchronous generator rated at 10 kVA, 230 V has an armature resistance of 0.5 ohm per phase and a synchronous reactance of 1.2 ohm per phase. Calculate the percentage voltage regulation at full load at power factors of (a) 0.8 lagging, (b) 0.8 leading, (c) determine the power factor such that the voltage regulation is zero on full load.

Given: star, 10 kVA, 230 V, Ra=0.5 ΩR_a = 0.5\ \Omega, Xs=1.2 ΩX_s = 1.2\ \Omega per phase.

Vph=2303=132.79 V,I=100003×230=25.10 AVcos⁡ϕ+IRa=106.23+12.55=118.78 VVsin⁡ϕ=79.67 V,IXs=30.12 V\begin{aligned} V_{ph} &= \frac{230}{\sqrt3} = 132.79\ \text{V},\quad I = \frac{10000}{\sqrt3\times230} = 25.10\ \text{A} \\ V\cos\phi + IR_a &= 106.23 + 12.55 = 118.78\ \text{V} \\ V\sin\phi &= 79.67\ \text{V},\quad IX_s = 30.12\ \text{V} \end{aligned}

(a) 0.8 pf lagging

E=118.782+(79.67+30.12)2=161.76 V%Reg=161.76−132.79132.79×100=21.81%\begin{aligned} E &= \sqrt{118.78^2 + (79.67 + 30.12)^2} = 161.76\ \text{V} \\ \%\text{Reg} &= \frac{161.76 - 132.79}{132.79}\times100 = 21.81\% \end{aligned}

(b) 0.8 pf leading

E=118.782+(79.67−30.12)2=128.70 V%Reg=128.70−132.79132.79×100=−3.08%\begin{aligned} E &= \sqrt{118.78^2 + (79.67 - 30.12)^2} = 128.70\ \text{V} \\ \%\text{Reg} &= \frac{128.70 - 132.79}{132.79}\times100 = -3.08\% \end{aligned}

(c) Power factor for zero regulation

Zero regulation means E=VE = V. With Zs=Ra+jXs=1.3∠67.38∘ ΩZ_s = R_a + jX_s = 1.3\angle 67.38^\circ\ \Omega and current I∠ϕI\angle\phi (ϕ\phi positive for leading):

E2=V2+2VIZscos⁡(θz+ϕ)+I2Zs2=V2cos⁡(θz+ϕ)=−IZs2V=−25.10×1.32×132.79=−0.1229θz+ϕ=97.06∘ϕ=97.06∘−67.38∘=29.68∘ (leading)pf=cos⁡29.68∘=0.869 leading\begin{aligned} E^2 &= V^2 + 2VIZ_s\cos(\theta_z + \phi) + I^2Z_s^2 = V^2 \\ \cos(\theta_z + \phi) &= -\frac{IZ_s}{2V} = -\frac{25.10\times1.3}{2\times132.79} = -0.1229 \\ \theta_z + \phi &= 97.06^\circ \\ \phi &= 97.06^\circ - 67.38^\circ = 29.68^\circ\ \text{(leading)} \\ \text{pf} &= \cos 29.68^\circ = 0.869\ \text{leading} \end{aligned}

Answer: (a) 21.81%; (b) −3.08%; (c) zero regulation at pf = 0.869 leading.