- Asked 2/14
- 2070 Bhadra · 8 marks
Sync generator (6600 V) leading voltage
Short answer
Full-load current I=1200kVA/(√3×6600V)=105 A/phase, Vph=3810 V. For 0.8 lagging, E=4249 V. For 0.8 leading, solving gives Vt=4560 V/phase, line voltage=7.90 kV.
A 1200 KVA, 6600 V, 3-phase star connected stator of a synchronous generator has an armature resistance of 0.4 Ω/phase and synchronous reactance of 6 Ω/phase. The generator delivers full load current at pf of 0.8 lagging at normal rated voltage. Calculate the terminal voltage for the same excitation and load current at 0.8 pf leading.
Given: 1200 kVA, 6600 V (line), 3-phase, star; R_a = 0.4 Ω/phase, X_s = 6 Ω/phase; full-load current at 0.8 pf lagging at rated voltage. Find the terminal voltage for the same excitation and current at 0.8 pf leading.
Step 1: Rated quantities
I = 1 200 000 / (√3 × 6600) = 104.97 A V_ph = 6600/√3 = 3810.5 V I R_a = 104.97 × 0.4 = 41.99 V; I X_s = 104.97 × 6 = 629.8 V
Step 2: Induced emf (0.8 lagging, cos φ = 0.8, sin φ = 0.6)
E = V + I (R_a + jX_s), where the current lags V by 36.87°:
E_real = V + IR cosφ + IX sinφ
= 3810.5 + 41.99(0.8) + 629.8(0.6)
= 3810.5 + 33.59 + 377.9 = 4222.0 V
E_imag = IX cosφ - IR sinφ
= 629.8(0.8) - 41.99(0.6) = 503.9 - 25.2 = 478.7 V
E = √(4222.0² + 478.7²) = 4249.1 V per phase
Step 3: Terminal voltage at 0.8 leading (same E, same I)
For a leading current:
- E_real = V_t + IR cos φ − IX sin φ = V_t + 33.59 − 377.9 = V_t − 344.3
- E_imag = IX cos φ + IR sin φ = 503.9 + 25.2 = 529.1
4249.1² = (Vt - 344.3)² + 529.1²
18 054 000 = (Vt - 344.3)² + 279 950
(Vt - 344.3)² = 17 774 000 -> Vt - 344.3 = 4216.0
Vt = 4560.3 V per phase
VL = √3 × 4560.3 = 7898.7 V
| Condition | Phase voltage | Line voltage |
|---|---|---|
| 0.8 lagging | 3810.5 V | 6600 V |
| 0.8 leading, same excitation | 4560 V | 7899 V |
Answer: terminal voltage ≈ 7.90 kV (line), 4560 V per phase.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Sync motor back emf at 0.5 pf leading · Electrical Machine, chapter 6
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1