Internal emf and armature reaction reactance
Short answer
Internal emf behind leakage impedance is 289.9 V per phase (502.1 V line). Armature reaction reactance Xa = Xs - Xl = 2.75 Ω per phase.
A 3-phase, star-connected, 60 kVA, 400 V, 50 Hz alternator has effective resistance of 0.25 Ω/ph. The synchronous reactance is 3.5 Ω/ph and leakage reactance is 0.75 Ω/ph. Determine at rated load and 0.8 lagging P.F (i) the internal emf Ei, (ii) the value of armature reactance which represents armature reaction.
Given: star, 60 kVA, 400 V, , , per phase; rated load at 0.8 pf lagging.
Phase voltage and current
(i) Internal emf
The internal (air-gap) emf is the voltage behind the leakage impedance :
(ii) Armature reactance (armature reaction)
Since :
E0
/|
/ | j I Xa (armature reaction)
/ |
/ + Ei
/ /| j I Xl
O---+-+ V + I Ra
`-.
`-. I (0.8 lag)
(For reference, the no-load emf using would be V per phase.)
Answer: (i) = 289.9 V per phase (502.1 V line); (ii) = 2.75 Ω per phase.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Internal emf, no-load emf and regulation · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- 1200 kVA alternator: voltage at leading pf · Electrical Machines, chapter 6 · asked 2×