- 2074 Chaitra · 7 marks
Internal emf, no-load emf and regulation
Short answer
Using leakage impedance, internal emf is 272.4 V per phase (471.8 V line). With synchronous impedance, no-load emf is 342.4 V per phase (593.0 V line), giving 34.77% regulation.
A star connected 50 kVA, 440 V, 50 Hz alternator has effective armature resistance of 0.25 Ω per phase, synchronous reactance is 3.2 Ω per phase and the leakage reactance is 0.5 Ω per phase. At rated load and unity power factor, Determine: (i) Internal emf (ii) No-load emf (iii) Percentage voltage regulation at full load
Given: star, 50 kVA, 440 V, , , leakage reactance per phase; rated load at unity pf.
- The internal (air-gap) emf is found using only the leakage impedance .
- The no-load emf (excitation emf) uses the full synchronous impedance , since includes armature reaction.
(i) Internal emf
(ii) No-load emf
(iii) Voltage regulation
E0
/|
/ | I Xa (armature reaction)
/ |
/ Ei+
/ / | I Xl
O-----+ V + I Ra
O-------> I (unity pf)
Answer: (i) = 272.4 V/phase (471.8 V line); (ii) = 342.4 V/phase (593.0 V line); (iii) regulation = 34.77%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Internal emf and armature reaction reactance · Electric Machines II, chapter 1
- Emf and regulation of 1500 kVA alternator · Electric Machines II, chapter 1 · asked 2×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Power angle and regulation of 10 kVA alternator · Electric Machines II, chapter 1
- 1600 kVA alternator: emf, regulation, power angle · Electrical Machines, chapter 6
- 1500 kVA alternator: excitation emf, voltage at leading pf · Electrical Machines, chapter 6
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6
- Design: 25 kVA transformer frame, regulation, tubes · Electric Machine Design, chapter 3 · asked 2×