Surge voltage at transformer with capacitance
Short answer
For steep surge, transformer represented by capacitance 0.002 uF; leakage inductance 16 H is neglected. Capacitance charges through 400 ohm from 2V source with time constant 0.8 us. Transformer voltage is 2000(1 - e^{-t/0.8 us}) kV, final maximum 2000 kV.
A 10 MVA, 132 kV transformer is connected to the end of the transmission line of surge impedance 400 Ω. The transformer has an equivalent capacitance of 0.002 μF and leakage inductance of 16 H. If a rectangular wave of 1000 kV travels through the line and strikes the transformer, find the surge voltage at the transformer.
For a steep surge (a few microseconds), the transformer behaves like its equivalent capacitance to ground. The leakage inductance of 16 H has a reactance so high at surge frequencies that it carries almost no current during this time, so it is neglected. A capacitance terminating a line of surge impedance charges through from a source of (Thevenin equivalent of the incident wave).
Z = 400 ohm
2V ~----/\/\/\----+---- V_C(t)
|
C = 0.002 uF
|
------------------+---- ground
Time constant
Voltage at the transformer terminal
| (μs) | (kV) |
|---|---|
| 0 | 0 |
| 0.8 | 1264 |
| 1.6 | 1729 |
| 2.4 | 1900 |
| 4.0 | 1987 |
At the capacitor acts as a short circuit, so the voltage is zero. It rises exponentially and finally reaches 2000 kV, the open-circuit (doubled) value.
Reflected wave
It starts at kV and becomes kV.
The capacitance does not reduce the final surge voltage. It only slopes the wavefront: the transformer voltage takes about s to reach 90% of the final value. This reduces the steepness and so the stress on the first few turns of the winding.
Answer: kV, with a final (maximum) value of 2000 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Surge on 400 Ω line terminated by 1000 Ω · High Voltage Engineering, chapter 3
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Surge from overhead line into cable and transformer · High Voltage Engineering, chapter 3
- Capacitance matrix of 400 kV bundled line · High Voltage Engineering, chapter 5 · asked 2×
- Cable to limit transformer surge voltage · High Voltage Engineering, chapter 3
- Significance of transmission voltage level, 132 vs 400 kV · Power System Analysis I, chapter 1
- Impedance diagram, 100 MVA 132 kV base, with load · Power System Analysis I, chapter 3
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- ACSR 132 kV line: parameters and charging MVA · Power System Analysis I, chapter 4