- 2082 Shrawan · 8 marks
Cable to limit transformer surge voltage
Short answer
Insert a cable of low surge impedance between line and transformer. Solving for 800 kV at transformer gives Zc ≈ 66.3 Ω; its junction voltage is 426.5 kV, so cable voltage rating is about 427 kV peak.
A transformer whose winding has a surge impedance of 1,000 Ω is to be connected to an overhead line with Z0 = 400 Ω. The lightning surge has a peak value of 1,500 kV coming in the line while the transformer voltage is to be limited to 800 kV, peak. Suggest an alternative to a lightning arrester by using a cable to connect the line to the transformer. Determine its surge impedance and voltage rating.
Instead of an arrester, a short length of cable of low surge impedance is inserted between the overhead line () and the transformer (). At the line–cable junction most of the surge is reflected back, so only a small voltage enters the cable; it then doubles (nearly) at the transformer. is chosen so that the transformer voltage is 800 kV.
Overhead line Cable Transformer
Z0 = 400 ohm ---- Zc ---------- Zt = 1000 ohm
1500 kV -> J1 J2
Assumption: only the first transmitted wave is considered (the cable is long enough that successive reflections inside it arrive after the surge crest).
Voltages
At junction J1 (line to cable):
At junction J2 (cable to transformer):
Condition kV
A cable has low surge impedance (30–70 Ω typical), so is taken. Any cable with keeps the transformer at or below 800 kV.
Voltage rating of the cable
Check: kV.
Without the cable, the transformer would see kV.
Answer: use a cable of surge impedance about 66.3 Ω with a surge (impulse) voltage rating of about 427 kV (peak); the transformer voltage is then limited to 800 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Surge from overhead line into cable and transformer · High Voltage Engineering, chapter 3
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Voltage rise at cable–overhead line junction · High Voltage Engineering, chapter 3 · asked 2×
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- LA 30 m from transformer, 3500 kV surge · High Voltage Engineering, chapter 4
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Three-point problem: A 800 m N, C 400 m W (500, 100, 300) · Engineering Geology I, chapter 5 · asked 4×
- EPS and book value; 500 shares, EBIT 40,000, tax 40% · Project Engineering, chapter 6
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5