Short answer

Insert a cable of low surge impedance between line and transformer. Solving for 800 kV at transformer gives Zc ≈ 66.3 Ω; its junction voltage is 426.5 kV, so cable voltage rating is about 427 kV peak.

A transformer whose winding has a surge impedance of 1,000 Ω is to be connected to an overhead line with Z0 = 400 Ω. The lightning surge has a peak value of 1,500 kV coming in the line while the transformer voltage is to be limited to 800 kV, peak. Suggest an alternative to a lightning arrester by using a cable to connect the line to the transformer. Determine its surge impedance and voltage rating.

Instead of an arrester, a short length of cable of low surge impedance ZcZ_c is inserted between the overhead line (Z0=400 ΩZ_0 = 400\ \Omega) and the transformer (Zt=1000 ΩZ_t = 1000\ \Omega). At the line–cable junction most of the surge is reflected back, so only a small voltage enters the cable; it then doubles (nearly) at the transformer. ZcZ_c is chosen so that the transformer voltage is 800 kV.

 Overhead line     Cable        Transformer
 Z0 = 400 ohm ---- Zc ---------- Zt = 1000 ohm
   1500 kV ->   J1           J2

Assumption: only the first transmitted wave is considered (the cable is long enough that successive reflections inside it arrive after the surge crest).

Voltages

At junction J1 (line to cable):

V1=2ZcZ0+Zc×1500V_1 = \frac{2Z_c}{Z_0 + Z_c}\times 1500

At junction J2 (cable to transformer):

V2=2ZtZc+ZtV1=1500×2Zc400+Zc×2000Zc+1000V_2 = \frac{2Z_t}{Z_c + Z_t}V_1 = 1500 \times \frac{2Z_c}{400 + Z_c}\times\frac{2000}{Z_c + 1000}

Condition V2=800V_2 = 800 kV

800(400+Zc)(1000+Zc)=1500×4000 Zc(400+Zc)(1000+Zc)=7500 ZcZc2+1400Zc+4×105=7500ZcZc2−6100Zc+4×105=0\begin{aligned} 800(400 + Z_c)(1000 + Z_c) &= 1500 \times 4000\,Z_c \\ (400 + Z_c)(1000 + Z_c) &= 7500\,Z_c \\ Z_c^2 + 1400Z_c + 4\times10^5 &= 7500Z_c \\ Z_c^2 - 6100Z_c + 4\times10^5 &= 0 \end{aligned} Zc=6100±61002−1.6×1062=6100±5967.42Z_c = \frac{6100 \pm \sqrt{6100^2 - 1.6\times10^6}}{2} = \frac{6100 \pm 5967.4}{2} Zc=66.3 Ωor6034 ΩZ_c = 66.3\ \Omega \quad \text{or} \quad 6034\ \Omega

A cable has low surge impedance (30–70 Ω typical), so Zc=66.3 ΩZ_c = 66.3\ \Omega is taken. Any cable with Zc≤66.3 ΩZ_c \le 66.3\ \Omega keeps the transformer at or below 800 kV.

Voltage rating of the cable

V1=2×66.3400+66.3×1500=426.5 kVV_1 = \frac{2 \times 66.3}{400 + 66.3}\times 1500 = 426.5\ \text{kV}

Check: V2=200066.3+1000×426.5=800V_2 = \frac{2000}{66.3 + 1000}\times 426.5 = 800 kV.

Without the cable, the transformer would see 2×10001400×1500=2143\frac{2 \times 1000}{1400}\times1500 = 2143 kV.

Answer: use a cable of surge impedance about 66.3 Ω with a surge (impulse) voltage rating of about 427 kV (peak); the transformer voltage is then limited to 800 kV.