- 2078 Chaitra · 8 marks
Surge from overhead line into cable and transformer
Short answer
Cable voltage = 2 × 100/(400+100) × 1000 = 400 kV. At the transformer (infinite impedance, open circuit) the voltage doubles to 2×400 = 800 kV.
An overhead line with Z0 = 400 ohms continues into a cable with Zc = 100 Ω. A surge with a crest value of 1000 kV is coming towards the junction from the overhead line. Calculate the voltage in the cable. Again, if the end of the cable is connected to a transformer whose impedance is practically infinite to a surge, when the bushing capacitance is omitted. Calculate the transformer voltage.
A travelling wave meeting a change of surge impedance is partly reflected and partly transmitted. The transmitted voltage is
Voltage entering the cable
(overhead line), (cable), kV.
Reflected voltage on the line kV. The low cable impedance greatly reduces the surge entering the cable.
Voltage at the transformer
The transformer has practically infinite surge impedance (bushing capacitance neglected), so the cable end behaves as an open circuit. The reflection coefficient is +1 and the voltage doubles:
OH line 400 ohm cable 100 ohm transformer
1000 kV ---> J1 ---- 400 kV ---> J2 (open: 800 kV)
Note: the reflected 400 kV wave from the transformer travels back to J1, where it is partly reflected again. Over successive reflections the transformer voltage settles towards kV (the open-end value for the original line). A short cable therefore only protects the transformer during the first few microseconds, unless an arrester is also used.
Answer: voltage in the cable = 400 kV; transformer voltage (first arrival) = 800 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage rise at cable–overhead line junction · High Voltage Engineering, chapter 3 · asked 2×
- Cable to limit transformer surge voltage · High Voltage Engineering, chapter 3
- Voltage build-up at line–cable junction · High Voltage Engineering, chapter 3
- Surge on 400 Ω line terminated by 1000 Ω · High Voltage Engineering, chapter 3
- Surge voltage at transformer with capacitance · High Voltage Engineering, chapter 3
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Fault at load end of overhead line · Power System Analysis II, chapter 3
- 400 km line at UPF: Zc, propagation, regulation · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- Regulation and efficiency of 100 km, 110 kV line · Power System Analysis I, chapter 6 · asked 2×