- 2070 Bhadra · 6 marks
Voltage build-up at line–cable junction
Short answer
At the junction, the transmitted voltage is VJ = 2Z2/(Z1+Z2) times the incident surge. With 500 kV, Z1=500 Ω and Z2=60 Ω, VJ = (120/560)×500 = 107.14 kV. A reflected wave of -392.86 kV returns on the line.
A transmission line of 500 Ω surge impedance is connected to a cable of 60 Ω surge impedance at other end. If a surge of 500 kV travels along the line to the junction point. Find the voltage build-up at the junctions?
At the junction of the line () and the cable (), the voltage that builds up equals the transmitted (refracted) wave:
Data: kV, (line), (cable).
Voltage at the junction
Reflected wave on the line
The reflection coefficient is . Most of the wave is reflected with negative sign, because the cable looks almost like a short circuit to the line.
Currents
- Incident: kA
- Transmitted into the cable: kA
- Reflected: kA, and ✓
line 500 ohm cable 60 ohm
500 kV ------> J ------> 107.14 kV
<------ -392.86 kV
This is why a short cable between an overhead line and a substation reduces the surge voltage entering the equipment.
Answer: voltage built up at the junction = 107.14 kV.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Voltage rise at cable–overhead line junction · High Voltage Engineering, chapter 3 · asked 2×
- Surge from overhead line into cable and transformer · High Voltage Engineering, chapter 3
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Surge impedance and travel time of 400 km line · High Voltage Engineering, chapter 3
- Cable to limit transformer surge voltage · High Voltage Engineering, chapter 3
- Arrester separation for a 500 kV/μs surge · High Voltage Engineering, chapter 4
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- Shunt generator voltage build-up, critical resistance and speed · Electrical Machines I, chapter 3 · asked 9×
- Voltage build-up, critical resistance and speed · Electrical Machines, chapter 3 · asked 3×
- Starting shunt generator on no load and voltage build-up · Electrical Machines I, chapter 3