Shunt generator voltage build-up, critical resistance and speed
Short answer
Residual magnetism induces a small EMF, driving field current. If field MMF aids residual flux, flux cumulatively increases, raising EMF until OCC intersects field resistance line. Critical field resistance is the maximum Rf that allows build-up (tangent to OCC). Critical speed Nc = N * Rf / Rc is the minimum speed for build-up with given Rf.
Explain the voltage build-up process of dc shunt generator and define the meaning of critical resistance and critical speed.
A self-excited DC shunt generator builds up its own field current from the small voltage due to residual magnetism, with no external DC source.
Voltage build-up process
+---------+-----------o +
| |
( G ) [Rsh] field V
| | winding
+---------+-----------o -
- The poles keep a little residual magnetism. When the armature is driven at rated speed, a small EMF (a few volts) is induced.
- This EMF drives a small current through the shunt field winding (connected across the armature).
- If the field is connected so that its MMF aids the residual flux, the flux increases, so the induced EMF increases.
- The higher EMF drives more field current, which increases flux further, and so on (cumulative process).
- Build-up stops where the OCC (magnetisation curve, vs ) meets the field resistance line (), because at that point the generated EMF just equals the drop across the field circuit. Saturation of the iron makes the OCC bend over, so the two curves intersect at a definite point.
E ^ field resistance line
| / (slope = Rf)
| / ___....--- OCC
| / .-'
| /.' <- operating point
| .' (OCC meets Rf line)
| .'/
| / / steps of build-up
| / /
|//
Er +------------------------> If
Critical field resistance
The critical field resistance is the maximum shunt-field circuit resistance at which the generator will just build up voltage at a given speed. It equals the slope of the tangent to the linear part of the OCC drawn from the origin. If , the field line lies above the OCC, they meet only near the residual voltage, and the machine fails to build up.
Critical speed
The critical speed is the minimum speed at which a shunt generator with a given field resistance will just build up. At that speed the slope of the OCC's initial tangent equals . Since EMF ∝ speed:
where is the critical resistance at speed .
Example: if at 1000 rpm and the field resistance is , then rpm.
Conditions for build-up
- Residual magnetism must be present.
- Field MMF must aid the residual flux (correct field connection / direction of rotation).
- Field circuit resistance must be less than critical resistance.
- Speed must be above critical speed.
- At start, load resistance should be high (no load), so the armature voltage is not pulled down.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Shunt generator build-up conditions, critical speed and resistance · Electrical Machines I, chapter 3
- Starting shunt generator on no load and voltage build-up · Electrical Machines I, chapter 3
- Critical resistance, critical speed and shunt generator characteristics · Electrical Machines I, chapter 3
- Voltage build-up in isolated induction generator · Electrical Machines I, chapter 5
- Voltage build-up, critical resistance and speed · Electrical Machines, chapter 3 · asked 3×
- Voltage build-up; series generator at no load · Electrical Machines, chapter 3
- DC shunt motor speed at reduced voltage and starting resistance · Utilization of Electrical Energy, chapter 3
- Voltage build-up in induction generator · Electrical Machines, chapter 5