Critical resistance, critical speed and shunt generator characteristics

Short answer

Critical resistance is the slope of the tangent to the OCC from the origin; the maximum field resistance allowing voltage build-up at a given speed. Critical speed is the minimum speed for build-up with a fixed field resistance, Nc = N·Rf/Rc. External characteristic: terminal voltage drops with load due to IaRa, armature reaction and reduced field current, turning back beyond critical load.

Define the terms critical resistance and critical speed of self-excited DC shunt generator with appropriate diagrams. Draw the performance characteristics of DC shunt generator and comment on it.

Critical field resistance

The critical field resistance RcR_c is the maximum resistance of the shunt field circuit at which a self-excited shunt generator will just build up voltage at a given speed. Graphically it is the slope of the tangent drawn from the origin to the initial (linear) part of the OCC.

  E ^      Rc line (tangent)
    |     /      Rf < Rc line
    |    /      /
    |   /     /   ____---- OCC (speed N)
    |  /    / .--'
    | /   /.-'   builds up here
    |/  ./
    | ./     Rf > Rc: no build-up
    |/
    +----------------------> If
  • Rf<RcR_f < R_c: field line cuts the OCC at a high voltage, so the machine builds up.
  • Rf>RcR_f > R_c: field line lies above the OCC; voltage stays near residual value.

Critical speed

The critical speed NcN_c is the speed at which a given field resistance RfR_f becomes the critical resistance, i.e. the minimum speed at which the generator just builds up. Since the OCC ordinates are proportional to speed:

NcN=RfRc⇒Nc=N RfRc\frac{N_c}{N} = \frac{R_f}{R_c} \quad\Rightarrow\quad N_c = N\,\frac{R_f}{R_c}
  E ^        Rf line
    |       /     OCC at N
    |      /   ___----
    |     /.--'
    |    //    OCC at Nc: tangent = Rf line
    |   //  __---
    |  //.-'
    | /.'     OCC below Nc: no build-up
    |/
    +----------------------> If

Example: Rc=220 ΩR_c = 220\ \Omega at 1500 rpm, Rf=176 ΩR_f = 176\ \Omega: Nc=1500×176/220=1200N_c = 1500 \times 176/220 = 1200 rpm.

Performance characteristics of DC shunt generator

1. Open-circuit characteristic (OCC, E0E_0 vs IfI_f): starts at the residual voltage, rises linearly, then bends due to saturation.

2. External characteristic (VV vs ILI_L):

  V ^
 E0 +----.___
    |        ''--.__        (a) drop: IaRa
    |               '--.    (b) drop: armature reaction
    |                   '.  (c) drop: lower If
    |                     \
    |              Ic   ,-'  turn-back
    |           <------'
    +------------------------> IL
    0     (short circuit current small)
  • Terminal voltage falls as load increases, because of (a) armature resistance drop IaRaI_aR_a, (b) armature reaction weakening flux, and (c) reduced field current since If=V/RfI_f = V/R_f falls with VV.
  • Beyond a critical load current IcI_c (load resistance below critical), the curve turns back: further decrease in load resistance lowers both VV and ILI_L. On a dead short circuit, the current is small (only residual EMF acts), so a shunt generator protects itself.

3. Internal characteristic (EE vs IaI_a): lies above the external curve by IaRaI_aR_a, showing the effect of armature reaction and reduced field current only.

Comment: the shunt generator gives an almost constant voltage for normal loads (voltage drop about 5-15% from no load to full load), so it is used for battery charging, excitation of alternators and lighting where moderate regulation is acceptable.

✓ Answer checked by Claude Opus 5.5 (high effort)