Arrester separation for a 500 kV/μs surge
Short answer
Protective ratio at zero distance is 500/420=1.19, below 1.25. At 40 m separation transformer voltage is 420+2*500*40/300=553.3 kV. Maximum distance for BIL is 24 m; no distance meets PR 1.25.
The arrester used in a line has its spark over voltage of 420 kV. A surge having steepness of 500 kV/μs on the front reaches the arrester terminal at time t = 0 and travels towards the transformer. BIL withstand voltage of the transformer is 500 kV and the PR required for transformer protection is 1.25. (i) Check whether the transformer is properly coordinated? (ii) Compute the voltage at the transformer terminal when the arrester is kept 40 m away from transformer. (iii) What is the maximum distance allowed between the transformer and the arrester in case of this surge? Assume that the residual voltage (discharge voltage) of the arrester is equal to its spark over voltage.
A surge reaching the arrester rises at kV/μs. It travels on to the transformer, metres beyond, and arrives after . The transformer (open end) doubles it, and the reflected wave gets back to the arrester at . From then on, the arrester voltage rises at , so the arrester sparks over at kV at time . The clamping effect takes a further time to reach the transformer, and until then the transformer voltage keeps rising. The standard result is
This holds when the reflection returns before the arrester would spark over on the incident wave alone, i.e. s ( m), which is true here.
(i) Coordination check (arrester right at the transformer)
The required PR is 1.25, which means the protective level must not exceed kV. Since kV, i.e. :
Not properly coordinated, even with zero separation.
(ii) Transformer voltage with the arrester 40 m away
This exceeds the BIL of 500 kV, so the transformer insulation would fail. The achieved PR is .
(iii) Maximum allowed distance
With PR = 1.25: the allowed transformer voltage is 400 kV, which is already below the arrester level of 420 kV. So no distance works ( is negative). The arrester rating must be lowered or the BIL raised.
Without margin, BIL = 500 kV:
500 kV/us d
----------> Arrester ----------- Transformer
(420 kV) (BIL 500 kV)
| Item | Result |
|---|---|
| PR at zero distance | 1.19 (< 1.25, not OK) |
| at 40 m | 553.3 kV |
| for PR 1.25 | none possible |
| for = BIL | 24 m |
Answer: (i) not coordinated (PR = 1.19); (ii) 553.3 kV; (iii) the arrester can be at most 24 m away to keep the voltage within the BIL. With the 1.25 margin, no distance satisfies the requirement.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Arrester 100 m from transformer coordination · High Voltage Engineering, chapter 4
- Transformer BIL and arrester resistance for 500 kV line · High Voltage Engineering, chapter 4
- Transformer BIL and maximum arrester distance · High Voltage Engineering, chapter 4
- Arrester with 1000 kV BIL on 300 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- Arrester with 1000 kV BIL on 350 Ω line · High Voltage Engineering, chapter 4 · asked 3×
- LA 30 m from transformer, 3500 kV surge · High Voltage Engineering, chapter 4
- 450 km 400 kV line, 420 MW, 0.95 pf · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- 4.2 kV/120 V transformer voltage regulation · Electrical Machines, chapter 2