- 2066 Magh (old course) · 8 marks
4.2 kV/120 V transformer voltage regulation
Short answer
Referred to secondary, equivalent resistance and reactance are 0.04114 Ω and 0.10286 Ω. No-load voltage E2 = √((120+500×0.04114)² + (500×0.10286)²) = 149.684 V. Voltage regulation = (149.684-120)/120×100 = 24.74%.
A 4.2 kV/120 V, 50 Hz, 1-phase transformer has following series parameters: , , , . If the transformer draws 500 A current on the secondary at rated terminal voltage, calculate voltage regulation at unity power factor.
Voltage regulation is the change in secondary terminal voltage from no load to load, as a fraction of the rated terminal voltage:
where is the no-load secondary voltage and is the load terminal voltage.
Equivalent parameters referred to secondary
No-load voltage at unity p.f.
With V, A and :
Regulation
Answer: voltage regulation at unity power factor (no-load secondary voltage V).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2
- Secondary voltage, regulation, pf for max regulation · Electrical Machines, chapter 2
- Voltage regulation of 2 MVA Δ-Y transformer · Electrical Machines I, chapter 2
- 250/500 V transformer, parameters both sides · Electrical Machines, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Emf and regulation of 1500 kVA 13 kV alternator · Electric Machines II, chapter 1