Design: 4000 kVA 66/11 kV power transformer
Short answer
Core: d = 436.8 mm, a = 371.3 mm, b = 231.5 mm. Frame: H = 1605.6 mm, W = 1854.5 mm, depth = 371.3 mm. Per-unit resistance drop ≈ 0.005, leakage reactance drop ≈ 0.048. Per-unit voltage regulation at 0.8 pf lag ≈ 0.033 (3.3%).
For a 4000 kVA, 3 phase, 50 Hz, 66 kV/11 kV, delta/delta, core type, oil immersed natural cooled power transformer the design data are: Max flux density in core = 1.6 Wb/m²; Constant for output voltage per turn = 0.6; Resistivity of copper = 0.021 Ω-mm²/m; Core type = Cruciform; Current density in conductors = 2.5 A/mm²; Window space factor = 0.22; Stacking factor = 0.9; Ratio of window height to width = 2.75; Take hot rolled steel and area of yoke is 20% greater than area of core; Width of duct between LV and core = 10 mm; Width of LV winding = 50 mm; Width of HV winding = 50 mm; Width of duct between LV and HV = 20 mm. Assuming all the other required parameters, calculate: (i) Overall core dimension (ii) Overall dimension of frame (iii) Per unit resistance and leakage reactance drop (iv) Per unit voltage regulation at 0.8 pf
Standard method (A.K. Sawhney). Assumptions: hot-rolled steel, yoke area = 1.2 × core area, yoke depth = largest stamping width, -mm²/m, end clearance 50 mm at each end of the 66 kV winding.
(i) Overall core dimensions
Voltage per turn, ( in kVA, total for 3 phases):
For a cruciform (two-stepped) core with stacking factor 0.9, (standard ratio, Sawhney):
Gross core area m².
Output equation (three phase):
Yoke
Yoke area 20% more than core area (hot-rolled steel, to reduce yoke loss and magnetising current). Yoke depth = width of largest stamping:
(ii) Overall dimensions of frame
+-----------------------------+ ---
| top yoke | ^
+-----+-----+-----+-----+-----+ |
|limb | |limb | |limb | |
| R | Ww | Y | Ww | B | H
| | | | | | |
+-----+-----+-----+-----+-----+ |
| bottom yoke | v
+-----------------------------+ ---
|<------------ W ------------>|
|<--- D --->|<--- D --->|
(iii) Per unit resistance and leakage reactance drop
Turns and conductors (both windings delta):
Phase voltages: LV (delta) V; HV (delta) V.
Phase currents: A; A.
Winding dimensions
Radial build (given clearance between core and LV = 10 mm):
| Item | Inside dia (mm) | Outside dia (mm) |
|---|---|---|
| LV winding | 456.8 | 556.8 |
| HV winding | 596.8 | 696.8 |
Radial depths: mm (LV), mm (HV), duct mm. Axial length mm.
Mean lengths of turn:
Check: HV outside diameter 697 mm < = 742 mm, leaving about 45 mm between adjacent HV coils.
Per unit resistance
Resistance referred to HV, with (copper at about 75 °C):
Per unit leakage reactance
Leakage reactance (per unit), with per limb and axial winding length mm:
(iv) Per unit regulation at 0.8 pf lagging
Answer: core = 437 mm; window 305 × 838 mm; frame 1606 × 1854 × 371 mm; = 0.0050, = 0.0479 p.u.; regulation ≈ 3.27%.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 100 kVA 4000/433 V distribution transformer · Electric Machine Design, chapter 3 · asked 4×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 125 kVA single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×