150 mile, 60 Hz line: ABCD and sending end
Short answer
Use long-line model with Z = 149.6∠79.27° Ω, Y = j6.786×10⁻⁴ S; γl = 0.3187∠84.63°, Zc = 469.6∠−5.37° Ω. A = D = 0.9506∠0.56°, B = 147.2∠79.45° Ω, C = 6.674×10⁻⁴∠90.18° S. Sending-end: V_S = 171.97 kV (line), I_S = 177.0 A, P_S = 45.64 MW at 0.8655 p.f. lagging.
A single circuit, 60 Hz, three phase transmission line is 150 miles long. The line is connected to a load of 50 MVA at a lagging power factor of 0.85 at 138 kV. The line constants are given as R = 0.1858 Ω/mile, L = 2.6 mH/mile, and C = 0.012 μF/mile. Determine the ABCD constants, sending end voltage, current and power.
Given: miles, 60 Hz; /mi, mH/mi, F/mi; load 50 MVA at 0.85 p.f. lagging, 138 kV. 150 miles (241 km) is treated with the exact long-line model.
Step 1: Per-mile and total constants
Step 2: and
Step 3: ABCD constants
Step 4: Receiving-end values
Step 5: Sending-end voltage and current
Step 6: Sending-end power
p.f. lagging
( MW, so the line loss is 3.14 MW and efficiency 93.12 %.)
Answer: , , S; kV (line), A, MW at 0.8655 p.f. lagging.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- 110 km, 110 kV line: sending end, regulation, efficiency · Power System Analysis I, chapter 6 · asked 2×
- 150 km line by T-model, 60 MW · Power System Analysis I, chapter 5
- Three-phase single-way controlled rectifier, α = 60° · Power Electronics, chapter 3 · asked 3×
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Three-phase single-way controlled rectifier, R load · Power Electronics, chapter 3 · asked 3×
- Fault at load end of overhead line · Power System Analysis II, chapter 3