150 mile, 60 Hz line: ABCD and sending end

Short answer

Use long-line model with Z = 149.6∠79.27° Ω, Y = j6.786×10⁻⁴ S; γl = 0.3187∠84.63°, Zc = 469.6∠−5.37° Ω. A = D = 0.9506∠0.56°, B = 147.2∠79.45° Ω, C = 6.674×10⁻⁴∠90.18° S. Sending-end: V_S = 171.97 kV (line), I_S = 177.0 A, P_S = 45.64 MW at 0.8655 p.f. lagging.

A single circuit, 60 Hz, three phase transmission line is 150 miles long. The line is connected to a load of 50 MVA at a lagging power factor of 0.85 at 138 kV. The line constants are given as R = 0.1858 Ω/mile, L = 2.6 mH/mile, and C = 0.012 μF/mile. Determine the ABCD constants, sending end voltage, current and power.

Given: l=150l = 150 miles, 60 Hz; R=0.1858 ΩR = 0.1858\ \Omega/mi, L=2.6L = 2.6 mH/mi, C=0.012 μC = 0.012\ \muF/mi; load 50 MVA at 0.85 p.f. lagging, 138 kV. 150 miles (241 km) is treated with the exact long-line model.

Step 1: Per-mile and total constants

z=0.1858+j(2π×60×2.6×10−3)=0.1858+j0.9802 Ω/miy=j2π×60×0.012×10−6=j4.524×10−6 S/miZ=zl=27.87+j147.03=149.6∠79.27∘ ΩY=yl=j6.786×10−4 S\begin{aligned} z &= 0.1858 + j(2\pi\times60\times2.6\times10^{-3}) = 0.1858 + j0.9802\ \Omega/\text{mi} \\ y &= j2\pi\times60\times0.012\times10^{-6} = j4.524\times10^{-6}\ \text{S/mi} \\ Z &= zl = 27.87 + j147.03 = 149.6\angle 79.27^\circ\ \Omega \\ Y &= yl = j6.786\times10^{-4}\ \text{S} \end{aligned}

Step 2: γl\gamma l and ZcZ_c

γl=ZY=0.3187∠84.63∘=0.02981+j0.31727Zc=Z/Y=469.6∠−5.37∘ Ω\begin{aligned} \gamma l &= \sqrt{ZY} = 0.3187\angle 84.63^\circ = 0.02981 + j0.31727 \\ Z_c &= \sqrt{Z/Y} = 469.6\angle -5.37^\circ\ \Omega \end{aligned}

Step 3: ABCD constants

A=D=cosh⁡γl=0.95051+j0.00930=0.9506∠0.56∘sinh⁡γl=0.02832+j0.31211=0.3134∠84.82∘B=Zcsinh⁡γl=147.2∠79.45∘ ΩC=sinh⁡γlZc=6.674×10−4∠90.18∘ S\begin{aligned} A = D &= \cosh\gamma l = 0.95051 + j0.00930 = 0.9506\angle 0.56^\circ \\ \sinh\gamma l &= 0.02832 + j0.31211 = 0.3134\angle 84.82^\circ \\ B &= Z_c\sinh\gamma l = 147.2\angle 79.45^\circ\ \Omega \\ C &= \frac{\sinh\gamma l}{Z_c} = 6.674\times10^{-4}\angle 90.18^\circ\ \text{S} \end{aligned}

Step 4: Receiving-end values

VR=1383=79.67∠0∘ kVIR=50×1063×138×103=209.2∠−31.79∘=177.81−j110.19 A\begin{aligned} V_R &= \frac{138}{\sqrt3} = 79.67\angle 0^\circ\ \text{kV} \\ I_R &= \frac{50\times10^6}{\sqrt3\times138\times10^3} = 209.2\angle -31.79^\circ = 177.81 - j110.19\ \text{A} \end{aligned}

Step 5: Sending-end voltage and current

VS=AVR+BIR=(75,732+j741)+(20,735+j22,755)=96,466+j23,496=99.29∠13.69∘ kV/phaseVS(L)=3×99.29=171.97 kVIS=CVR+DIR=(−0.17+j53.17)+(170.03−j103.09)=169.86−j49.92=177.0∠−16.38∘ A\begin{aligned} V_S &= AV_R + BI_R = (75{,}732 + j741) + (20{,}735 + j22{,}755) \\ &= 96{,}466 + j23{,}496 = 99.29\angle 13.69^\circ\ \text{kV/phase} \\ V_{S(L)} &= \sqrt3\times99.29 = 171.97\ \text{kV} \\ I_S &= CV_R + DI_R = (-0.17 + j53.17) + (170.03 - j103.09) \\ &= 169.86 - j49.92 = 177.0\angle -16.38^\circ\ \text{A} \end{aligned}

Step 6: Sending-end power

p.f. =cos⁡(13.69∘+16.38∘)=cos⁡30.07∘=0.8655= \cos(13.69^\circ + 16.38^\circ) = \cos 30.07^\circ = 0.8655 lagging

PS=3∣VS∣∣IS∣cos⁡ϕS=3×99.29×103×177.0×0.8655=45.64 MWQS=26.42 Mvar\begin{aligned} P_S &= 3|V_S||I_S|\cos\phi_S = 3\times99.29\times10^3\times177.0\times0.8655 = 45.64\ \text{MW} \\ Q_S &= 26.42\ \text{Mvar} \end{aligned}

(PR=42.5P_R = 42.5 MW, so the line loss is 3.14 MW and efficiency 93.12 %.)

Answer: A=D=0.9506∠0.56∘A = D = 0.9506\angle 0.56^\circ, B=147.2∠79.45∘ ΩB = 147.2\angle 79.45^\circ\ \Omega, C=6.674×10−4∠90.18∘C = 6.674\times10^{-4}\angle 90.18^\circ S; VS=171.97V_S = 171.97 kV (line), IS=177.0I_S = 177.0 A, PS=45.64P_S = 45.64 MW at 0.8655 p.f. lagging.