- 2083 Baishakh (new course) · 4+3 marks
Critical clearing for temporary sending-end fault
Short answer
Critical clearing angle from equal area criterion is 84.78°. Critical clearing time, computed from the swing equation with zero accelerating power, is 0.26 s (about 15.6 cycles at 60 Hz).
A 60 Hz synchronous generator has inertia constant H = 5 MJ/MVA and a direct axis transient reactance Xd' = 0.3 p.u. connected to an infinite bus V = 1∠0°. The generator has internal emf E' = 1.17∠26.387° p.u. and Pe = 0.8 p.u. The reactance of transformer and both transmission line are in p.u. A temporary 3-phase fault occurs at the sending end of the line at point 'F'. When the fault is cleared, both the lines is intact. Determine the critical clearing angle and the critical clearing time. [Figure: generator E' = 1.17∠26.387°, Xd' = 0.3 - transformer Xt = 0.2 - bus 1; two parallel lines Xl = 0.3 each (breakers at both ends) from bus 1 to bus 2, the infinite bus V = 1∠0°; fault F at bus 1 (sending end)]
Data: Hz, MJ/MVA, , , (each of two lines), , , pu.
Step 1: Pre-fault power-angle curve
Check: pu, so rad.
Step 2: During and after the fault
- The fault is at the sending end (bus 1), whose voltage becomes zero. So during the fault.
- The fault is temporary and both lines stay intact after clearing, so the post-fault curve is the same as before: .
Step 3: Critical clearing angle
From the equal area criterion, with and :
Step 4: Critical clearing time
With , :
Answer: Critical clearing angle ; critical clearing time s (about 15.6 cycles at 60 Hz).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing angle, Pmax 2, 0.5, 1.5 · Power System Analysis II, chapter 6
- Inertia constant on 500 MVA base · Power System Analysis II, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3