- 2078 Bhadra · 12 marks
Critical clearing time, H = 8 MJ/MVA
Short answer
Pre-fault Pmax=1.5385 pu, delta0=40.54°. Post-fault Pmax=1.25 pu, delta_max=126.87°. Equal area gives delta_cr=52.74°. Then t_cr = 0.147 s (assuming E=1 pu).
In the power system network shown below, if the generator delivers 1 pu real power at infinite bus 2. A 3-phase bolted fault occurs at the end of the 1st transmission line. The fault is isolated by simultaneous opening of circuit breakers on the both end of the line. Find the critical fault clearing time so that transient stability of the machine is maintained. Inertia constant of the generator is 8 MJ/MVA. [Figure: generator E∠δ with X'd = 0.3 - transformer j0.2 - bus 1; two parallel lines L1 (j0.3) and L2 (j0.3) with breakers at both ends between bus 1 and bus 2; infinite bus 1∠0° at bus 2]
Assumption: the internal emf magnitude is not given in the figure, so pu and Hz are assumed. The method is the same for any other .
Data: , , pu, pu, MJ/MVA, .
Step 1: Pre-fault
Step 2: During the fault
The fault is at the end of line 1, either at bus 1 or at the infinite bus 2. In both cases one of the buses on the power path is at zero voltage, so and the power transferred is zero.
Step 3: Post-fault (line 1 removed)
Since , the system can be stable if the fault is cleared in time.
Step 4: Critical clearing angle
Step 5: Critical clearing time
With during the fault, . So
Answer (with pu): , critical clearing time s (about 7.4 cycles).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- Critical clearing angle and time, H = 2 · Power System Analysis II, chapter 6
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4