Critical clearing time, H = 8 MJ/MVA

Short answer

Pre-fault Pmax=1.5385 pu, delta0=40.54°. Post-fault Pmax=1.25 pu, delta_max=126.87°. Equal area gives delta_cr=52.74°. Then t_cr = 0.147 s (assuming E=1 pu).

In the power system network shown below, if the generator delivers 1 pu real power at infinite bus 2. A 3-phase bolted fault occurs at the end of the 1st transmission line. The fault is isolated by simultaneous opening of circuit breakers on the both end of the line. Find the critical fault clearing time so that transient stability of the machine is maintained. Inertia constant of the generator is 8 MJ/MVA. [Figure: generator E∠δ with X'd = 0.3 - transformer j0.2 - bus 1; two parallel lines L1 (j0.3) and L2 (j0.3) with breakers at both ends between bus 1 and bus 2; infinite bus 1∠0° at bus 2]

Assumption: the internal emf magnitude is not given in the figure, so ∣E∣=1.0|E| = 1.0 pu and f=50f = 50 Hz are assumed. The method is the same for any other EE.

Data: Xd′=0.3X_d' = 0.3, XT=0.2X_T = 0.2, L1=L2=0.3L_1 = L_2 = 0.3 pu, Pm=1P_m = 1 pu, H=8H = 8 MJ/MVA, V=1∠0∘V = 1\angle0^\circ.

Step 1: Pre-fault

XI=0.3+0.2+0.32=0.65 puPmax1=1×10.65=1.5385 puδ0=sin⁡−111.5385=40.54∘=0.7076 rad\begin{aligned} X_I &= 0.3 + 0.2 + \frac{0.3}{2} = 0.65\ \text{pu} \\ P_{max1} &= \frac{1\times1}{0.65} = 1.5385\ \text{pu} \\ \delta_0 &= \sin^{-1}\frac{1}{1.5385} = 40.54^\circ = 0.7076\ \text{rad} \end{aligned}

Step 2: During the fault

The fault is at the end of line 1, either at bus 1 or at the infinite bus 2. In both cases one of the buses on the power path is at zero voltage, so Pmax2=0P_{max2} = 0 and the power transferred is zero.

Step 3: Post-fault (line 1 removed)

XIII=0.3+0.2+0.3=0.8 puPmax3=10.8=1.25 puδmax=180∘−sin⁡−111.25=126.87∘=2.2143 rad\begin{aligned} X_{III} &= 0.3 + 0.2 + 0.3 = 0.8\ \text{pu} \\ P_{max3} &= \frac{1}{0.8} = 1.25\ \text{pu} \\ \delta_{max} &= 180^\circ - \sin^{-1}\frac{1}{1.25} = 126.87^\circ = 2.2143\ \text{rad} \end{aligned}

Since Pmax3>PmP_{max3} > P_m, the system can be stable if the fault is cleared in time.

Step 4: Critical clearing angle

cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmaxPmax3=1(2.2143−0.7076)+1.25cos⁡126.87∘1.25=1.5067−0.751.25=0.6054δcr=52.74∘=0.9206 rad\begin{aligned} \cos\delta_{cr} &= \frac{P_m(\delta_{max}-\delta_0) + P_{max3}\cos\delta_{max}}{P_{max3}} \\ &= \frac{1(2.2143-0.7076) + 1.25\cos 126.87^\circ}{1.25} \\ &= \frac{1.5067 - 0.75}{1.25} = 0.6054 \\ \delta_{cr} &= 52.74^\circ = 0.9206\ \text{rad} \end{aligned}

Step 5: Critical clearing time

With Pe=0P_e = 0 during the fault, δ=δ0+πfPm2Ht2\delta = \delta_0 + \dfrac{\pi f P_m}{2H}t^2. So

tcr=2H(δcr−δ0)πfPm=2×8×(0.9206−0.7076)π×50×1=0.147 s\begin{aligned} t_{cr} &= \sqrt{\frac{2H(\delta_{cr}-\delta_0)}{\pi f P_m}} \\ &= \sqrt{\frac{2\times 8\times(0.9206-0.7076)}{\pi\times 50\times 1}} \\ &= 0.147\ \text{s} \end{aligned}

Answer (with E=1.0E = 1.0 pu): δcr=52.74∘\delta_{cr} = 52.74^\circ, critical clearing time tcr≈0.147t_{cr} \approx 0.147 s (about 7.4 cycles).

✓ Answer checked by Claude Sonnet 5.5