Critical clearing angle, Pm = 1.2 pu

Short answer

Pre-fault Pmax=3.143 pu, delta0=22.45°. During fault Pe=0. Post-fault Pmax=2 pu, delta_max=143.13°. Equal area gives delta_cr = 62.37°.

For the system shown in figure, the per unit values of different quantities are E = 1.1, V = 1, Xd' = 0.15, X1 = X2 = 0.4. The system is operating in equilibrium with Pm = 1.2 pu. Find the critical clearing angle if a 3-phase fault occurs on line-2 close to the generator. [Figure: generator E∠δ behind Xd' feeding two parallel lines X1 and X2 (each with circuit breakers at both ends) to an infinite bus V∠0; fault F at the generator end of line 2]

Data: E=1.1E = 1.1, V=1V = 1, Xd′=0.15X_d' = 0.15, X1=X2=0.4X_1 = X_2 = 0.4 pu, Pm=1.2P_m = 1.2 pu. The fault is on line 2 close to the generator and is cleared by opening line 2.

Step 1: Pre-fault (both lines in service)

XI=0.15+0.42=0.35 puPmax1=1.1×10.35=3.143 puδ0=sin⁡−11.23.143=22.45∘=0.3918 rad\begin{aligned} X_I &= 0.15 + \frac{0.4}{2} = 0.35\ \text{pu} \\ P_{max1} &= \frac{1.1\times 1}{0.35} = 3.143\ \text{pu} \\ \delta_0 &= \sin^{-1}\frac{1.2}{3.143} = 22.45^\circ = 0.3918\ \text{rad} \end{aligned}

Step 2: During the fault

The fault is at the generator end of line 2, which is the generator-side bus. That bus is at zero voltage, so no power reaches the infinite bus: Pmax2=0P_{max2} = 0.

Step 3: Post-fault (line 2 open)

XIII=0.15+0.4=0.55 puPmax3=1.10.55=2.0 puδmax=180∘−sin⁡−11.22.0=180∘−36.87∘=143.13∘=2.4981 rad\begin{aligned} X_{III} &= 0.15 + 0.4 = 0.55\ \text{pu} \\ P_{max3} &= \frac{1.1}{0.55} = 2.0\ \text{pu} \\ \delta_{max} &= 180^\circ - \sin^{-1}\frac{1.2}{2.0} = 180^\circ - 36.87^\circ = 143.13^\circ = 2.4981\ \text{rad} \end{aligned}

Step 4: Critical clearing angle

From A1=A2A_1 = A_2:

cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmax−Pmax2cos⁡δ0Pmax3−Pmax2\cos\delta_{cr} = \frac{P_m(\delta_{max}-\delta_0) + P_{max3}\cos\delta_{max} - P_{max2}\cos\delta_0}{P_{max3}-P_{max2}} cos⁡δcr=1.2(2.4981−0.3918)+2.0cos⁡143.13∘−02.0−0=2.5276−1.60002.0=0.4638δcr=62.37∘\begin{aligned} \cos\delta_{cr} &= \frac{1.2(2.4981-0.3918) + 2.0\cos 143.13^\circ - 0}{2.0 - 0} \\ &= \frac{2.5276 - 1.6000}{2.0} = 0.4638 \\ \delta_{cr} &= 62.37^\circ \end{aligned}

Answer: Critical clearing angle δcr≈62.37∘\delta_{cr} \approx 62.37^\circ.