- 2079 Bhadra · 8 marks
Critical clearing angle, Pm = 1.2 pu
Short answer
Pre-fault Pmax=3.143 pu, delta0=22.45°. During fault Pe=0. Post-fault Pmax=2 pu, delta_max=143.13°. Equal area gives delta_cr = 62.37°.
For the system shown in figure, the per unit values of different quantities are E = 1.1, V = 1, Xd' = 0.15, X1 = X2 = 0.4. The system is operating in equilibrium with Pm = 1.2 pu. Find the critical clearing angle if a 3-phase fault occurs on line-2 close to the generator. [Figure: generator E∠δ behind Xd' feeding two parallel lines X1 and X2 (each with circuit breakers at both ends) to an infinite bus V∠0; fault F at the generator end of line 2]
Data: , , , pu, pu. The fault is on line 2 close to the generator and is cleared by opening line 2.
Step 1: Pre-fault (both lines in service)
Step 2: During the fault
The fault is at the generator end of line 2, which is the generator-side bus. That bus is at zero voltage, so no power reaches the infinite bus: .
Step 3: Post-fault (line 2 open)
Step 4: Critical clearing angle
From :
Answer: Critical clearing angle .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing angle, breakers 1 and 2 · Power System Analysis II, chapter 6 · asked 2×
- Initial rotor angle and critical clearing angle · Power System Analysis II, chapter 6
- Critical clearing angle and time, H = 2 · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Per unit circuit of three-generator system, 30 MVA base · Power System Analysis I, chapter 3
- Per unit values: 100 MVA generator, two motors · Power System Analysis I, chapter 3
- Two-mass system X1/F, X2/F with F-V analogy · Control Systems, chapter 2 · asked 3×
- Free body diagram and X1/F, X2/F of two-mass system · Control Systems, chapter 2