- 2082 Baishakh · 8 marks
Critical clearing angle/time, fault at infinite bus
Short answer
Pre-fault Pmax=2 pu, delta0=30°. During fault Pe=0. Equal area gives delta_cr=79.56°. Then t_cr = sqrt(2H(delta_cr-delta0)/(pi f Pm)) = 0.235 s.
A 50 Hz synchronous generator connected to infinite bus as shown in the figure below has a H constant of 5 p.u. Under normal condition (just before disturbance), the generator injects 1 p.u. real power to the infinite bus with generator excitation voltage of 1.1 p.u. and infinite bus voltage 1 p.u. Suddenly a 3-phase bolted fault occurs at the infinite bus. Compute the critical fault clearing angle and critical fault clearing time for system to be transient stable. [Figure: generator X = 10%, transformer X = 5%, two parallel lines each X = 0.8 pu, to the infinite bus]
Data: MJ/MVA, Hz, pu, pu, pu, , , two parallel lines of pu each.
Assumption: the fault is a temporary fault at the infinite bus. After it is cleared, the network is the same as before the fault.
Step 1: Pre-fault power-angle curve
Step 2: During and after the fault
A bolted fault at the infinite bus makes , so and during the fault.
After clearing, pu. Then
Step 3: Critical clearing angle (equal areas)
Setting gives
Step 4: Critical clearing time
With during the fault, the swing equation is . Integrating twice:
Answer: Critical clearing angle ; critical clearing time s (about 11.7 cycles).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Critical clearing angle and time, H = 2 · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Initial rotor angle and critical clearing angle · Power System Analysis II, chapter 6
- Critical clearing angle, Pmax 2, 0.5, 1.5 · Power System Analysis II, chapter 6
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Why infinite bus frequency and voltage stay constant · Power System Analysis I, chapter 1
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Time of critical DO deficit, 50 l/s city · Sanitary Engineering, chapter 6 · asked 2×