- 2071 Shrawan · 6 marks
Power transfer and pf of motor on infinite bus
Short answer
With Ef = 1.5∠120° pu, power transfer = 1.443 pu = 14.43 MW delivered to bus (generating); power factor = 0.596 leading. If Ef angle is -120°, motor absorbs 14.43 MW at 0.596 lagging.
A 3 phase, 10 MVA, 2300 V, 60 Hz synchronous motor has Xs = 0.9 pu and negligible stator resistance. The motor is connected to infinite bus. If terminal voltage, Vt = 2300∠0 V and excitation emf Ef = 3450∠120 V [printed "3450V<120"]. Determine power transfer and power factor of machine. Also draw phasor diagram.
Reading of data: V and V are taken as line values (the rating is 2300 V line), with at as printed. Work in per unit on 10 MVA, 2300 V.
Power transfer
Current and power factor
Using the motor equation :
The real part is negative: since leads , the machine is not taking power; it is delivering 14.43 MW to the bus, i.e. acting as a generator. Taking the generated current pu, it leads by :
Ef (1.5 pu)
\
\ at 120 deg from Vt
\
O-----------> Vt (1.0 pu)
\
\ Ia (motor convention)
v at -126.6 deg
jXs.Ia = Vt - Ef joins tip of Ef to tip of Vt
Ia(gen) = -Ia leads Vt by 53.4 deg
Note: with the machine is beyond the steady-state limit () and the current (2.42 pu) is far above rating, so this point is not a stable working point. If the angle was meant as (motor action, lagging), the same magnitudes result: the motor absorbs 14.43 MW at a pf of 0.596 lagging.
Answer: Power transferred pu MW; power factor (leading as printed, i.e. generating; lagging if is at ).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- 25 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- 30 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- 20 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Current, pf, power and efficiency of 3.3 kV motor · Electric Machines II, chapter 2
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Generator reactive power at constant terminal voltage · Power System Analysis II, chapter 1
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6