- 2071 Shrawan · 6 marks
Generator on infinite bus with 15% excitation rise
Short answer
At rated kVA, 0.8 pf lagging, excitation is 231.7 V per phase, power angle 28.63°. After 15% field increase with constant turbine power, stator current is 16.51 A, pf 0.673 lagging, active power 4.0 kW, reactive power 4.40 kVAR.
A 3-phase, 5 kVA, 208 V, 4-pole, 60 Hz, star connected synchronous generator has negligible armature winding resistance and synchronous reactance of 10 ohms per phase. The generator is first connected to an infinite bus of 208 V, 60 Hz. i) Determine the excitation voltage and the power angle when the generator is delivering rated kVA at 0.8 pf lagging. ii) If the field excitation is now increased by 15% (keeping turbine power constant), find the stator current, power factor, active and reactive power constant.
Given: star, 5 kVA, 208 V, 60 Hz, , , on a 208 V, 60 Hz infinite bus.
(i) Excitation voltage and power angle at rated kVA, 0.8 pf lagging
W, VAR.
(ii) Excitation increased by 15%, turbine power constant
Active and reactive power
Increasing the field only raises the reactive power supplied to the bus; active power is set by the turbine.
Answer: (i) E = 231.7 V/phase (401.3 V line), δ = 28.63°; (ii) I = 16.51 A, pf = 0.673 lagging, P = 4.0 kW (constant), Q = 4.40 kVAR.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator on bus with 20% excitation increase · Electric Machines II, chapter 1
- Excitation emf of salient pole generator · Electric Machines II, chapter 1
- Regulation of 10 kVA round-rotor generator · Electric Machines II, chapter 1
- Back emf and new current of 5 kVA motor · Electric Machines II, chapter 2 · asked 3×
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Merz-Price: unprotected winding (5000 kVA) · Switchgear and Protection, chapter 7 · asked 2×
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Neutral reactance for 15 MVA generator · Power System Analysis II, chapter 5