- 2071 Chaitra · 6 marks
Generator on bus with 20% excitation increase
Short answer
At rated kVA, 0.8 pf lagging, excitation voltage is 206.8 V per phase, power angle 25.44°. With 20% higher excitation and constant prime mover power, stator current becomes 17.83 A at 0.623 lagging pf.
A 3-phase, 5 kVA, 208 V, 4-pole, 50 Hz star connected synchronous machine has negligible stator winding resistance and synchronous reactance of 8 Ω/phase. The machine is operated as generator in parallel with 3-phase, 208 V and 50 Hz supply. Then, i) Determine the excitation voltage and power angle when machine is delivering rated kVA at 0.8 pf lagging. ii) If the excitation is increased by 20% without changing prime mover power, find the stator current and power factor.
Given: star, 5 kVA, 208 V, 50 Hz, , , in parallel with a 208 V bus (infinite bus).
(i) Excitation voltage and power angle at rated kVA, 0.8 pf lagging
Check: W kW.
(ii) Excitation increased by 20%, same input power
The active current component stays 11.10 A (power unchanged); extra excitation only increases the lagging reactive current, so the generator supplies more reactive power ( rises from 3 kVAR to 5.02 kVAR).
Answer: (i) E = 206.8 V/phase (358.1 V line), δ = 25.44°; (ii) I = 17.83 A, pf = 0.623 lagging.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Back emf and new current of 5 kVA motor · Electric Machines II, chapter 2 · asked 3×
- Excitation emf of salient pole generator · Electric Machines II, chapter 1
- 20 MVA salient pole motor maximum power · Electric Machines II, chapter 2 · asked 3×
- Synchronous reactance and regulation from test data · Electric Machines II, chapter 1
- Salient pole motor excitation and reluctance power · Electric Machines II, chapter 2
- Reactance diagram: 20 MVA generator, 15 kV/25 MVA base · Power System Analysis I, chapter 3
- Merz-Price: unprotected winding (5000 kVA) · Switchgear and Protection, chapter 7 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Excitation capacitors in isolated and grid-connected induction generator · Electrical Machines I, chapter 5