- 2073 Shrawan · 6 marks
Generator reactive power at constant terminal voltage
Short answer
With constant prime mover power, adjusting field excitation changes internal emf Ef, shifting the reactive power output while terminal voltage Vt stays fixed by the infinite bus. Over-excitation supplies lagging reactive power; under-excitation absorbs leading reactive power, subject to field heating and stability limits.
For a synchronous generator connected to infinite bus, discuss how the generator can supply or consume variable reactive power keeping its terminal voltage constant.
A synchronous generator on an infinite bus has its terminal voltage and frequency fixed by the bus. With constant mechanical input (constant P), it can still be made to supply or absorb any reactive power within limits by changing its field excitation.
Equations
With synchronous reactance (R neglected), internal emf and load angle :
- P depends on the turbine input; since and are fixed, = constant. So as changes, the tip of moves along a line parallel to .
- (active current) also remains constant.
- Q depends on , which changes with excitation.
Three cases
| Excitation | Condition | Q | Power factor |
|---|---|---|---|
| Normal | 0 | Unity | |
| Over-excited | Supplied (+) | Lagging | |
| Under-excited | Absorbed (−) | Leading |
locus of Ef tip (P constant)
--------x-------x--------x-------
/ / /
Ef1 / Ef2 / Ef3 / Ef1 < Ef2 < Ef3
/ / /
O--------------------> Vt
Ef1: under-excited (absorbs Q)
Ef3: over-excited (supplies Q)
Explanation
- Increasing field current raises ; decreases and swings to lagging. The generator sends Q into the bus.
- Decreasing field current lowers ; increases and becomes leading. The generator draws Q from the bus.
- Terminal voltage remains constant because the infinite bus holds it.
Limits
Maximum Q is set by field heating (maximum ) and armature current; minimum Q (maximum absorption) by the steady-state stability limit ( near 90°) and stator end heating. This is how generators are used for voltage/Q support in a real grid.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Reactive power injection and generation limits · Power System Analysis II, chapter 1
- Rotor angle and swing equation, infinite bus · Power System Analysis II, chapter 6
- Fault at generator terminal feeding motor · Power System Analysis II, chapter 3
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Reactive power and voltage balance · Power System Analysis II, chapter 1
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Why infinite bus frequency and voltage stay constant · Power System Analysis I, chapter 1
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Sync generator terminal voltage, leading pf · Electrical Machine, chapter 6 · asked 2×