- 2068 Chaitra · 8 marks
Critical clearing, fault at infinite bus, H = 6
Short answer
Using the equal area criterion with zero electrical power during the fault yields a critical clearing angle of 79.56°. The swing equation with constant acceleration gives a critical clearing time of 0.257 s (12.9 cycles).
A 3-phase, 50 Hz generator is connected to an infinite bus via transmission line. The inertia constant of the generator is 6 MJ/MVA and mechanical power input is 1.0 pu. The maximum power that can be delivered by generator is 2.0 pu. A 3-phase fault occurs at the infinite bus. Determine the critical clearing angle and critical clearing time.
Data: Hz, MJ/MVA, pu, pu.
Assumption: the fault is at the infinite bus and is temporary, so during the fault. After clearing, the original curve is restored.
Step 1: Initial and maximum angles
Step 2: Critical clearing angle
Accelerating area:
Decelerating area:
Setting with and :
Step 3: Critical clearing time
During the fault the swing equation is . Integrating twice from rest at :
Answer: Critical clearing angle ; critical clearing time s (about 12.9 cycles).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing angle, Pmax 2, 0.5, 1.5 · Power System Analysis II, chapter 6
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Line with 50+j50 load, first maximum, power · Electromagnetism, chapter 5
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×