- 2078 Kartik · 10 marks
Critical clearing angle, Pmax 2, 0.5, 1.5
Short answer
Pre-fault Pmax=2 pu gives delta0=30°, post-fault Pmax=1.5 pu gives delta_max=138.19°. Using equal area, delta_cr = 70.3°.
A 50 Hz generator with inertia constant 5 MJ/MVA is delivering 1 pu power to an infinite bus. When a fault occurs, the maximum power transferable reduces to 0.5 pu. The maximum power transferable before the occurrence of fault was 2 pu. The maximum power after clearance of fault is 1.5 pu. Compute the critical fault clearing angle.
Data: pu, pu (pre-fault), pu (during fault), pu (post-fault), MJ/MVA, Hz. is not needed for the angle.
Step 1: Initial and maximum angles
Step 2: Equal area condition
Accelerating area (from to on curve 2) = decelerating area (from to on curve 3):
This gives
Step 3: Substitute
Answer: Critical clearing angle .
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- Critical clearing angle, Pmax 1.5, 0.5, 1.2 · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Bus-bar reactor scheme: 30 MVA and 50 MVA · Power Plant Equipment, chapter 4 · asked 2×
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2
- Why infinite bus frequency and voltage stay constant · Power System Analysis I, chapter 1