Critical clearing angle, Pmax 1.5, 0.5, 1.2

Short answer

Given pre-fault, fault, and post-fault power maxima (1.5, 0.5, 1.2 pu) and mechanical power 0.9 pu, the equal area criterion yields a critical clearing angle of approximately 65.4°.

A generator is delivering 0.9 pu to an infinite bus through a purely reactive transmission line. Maximum power that could be delivered is 1.5 pu. A fault occurs such that maximum electrical power output reduces to 0.5 pu. When the fault is cleared, the maximum power that can be delivered is 1.2 pu. Determine the critical clearing angle using equal area criterion.

Data: Pm=0.9P_m = 0.9 pu, Pmax1=1.5P_{max1} = 1.5 pu (pre-fault), Pmax2=0.5P_{max2} = 0.5 pu (during fault), Pmax3=1.2P_{max3} = 1.2 pu (post-fault). The line is purely reactive, so there are no losses.

Step 1: Angles

δ0=sin⁡−10.91.5=36.87∘=0.6435 radδmax=180∘−sin⁡−10.91.2=180∘−48.59∘=131.41∘=2.2935 rad\begin{aligned} \delta_0 &= \sin^{-1}\frac{0.9}{1.5} = 36.87^\circ = 0.6435\ \text{rad} \\ \delta_{max} &= 180^\circ - \sin^{-1}\frac{0.9}{1.2} = 180^\circ - 48.59^\circ = 131.41^\circ = 2.2935\ \text{rad} \end{aligned}

Step 2: Equal area criterion

∫δ0δcr(Pm−Pmax2sin⁡δ) dδ=∫δcrδmax(Pmax3sin⁡δ−Pm) dδ\int_{\delta_0}^{\delta_{cr}}(P_m - P_{max2}\sin\delta)\,d\delta = \int_{\delta_{cr}}^{\delta_{max}}(P_{max3}\sin\delta - P_m)\,d\delta ⇒ cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmax−Pmax2cos⁡δ0Pmax3−Pmax2\Rightarrow\ \cos\delta_{cr} = \frac{P_m(\delta_{max}-\delta_0) + P_{max3}\cos\delta_{max} - P_{max2}\cos\delta_0}{P_{max3}-P_{max2}}

Step 3: Substitute

cos⁡δcr=0.9(2.2935−0.6435)+1.2cos⁡131.41∘−0.5cos⁡36.87∘1.2−0.5=1.4850−0.7937−0.40000.7=0.4161δcr=65.41∘\begin{aligned} \cos\delta_{cr} &= \frac{0.9(2.2935-0.6435) + 1.2\cos131.41^\circ - 0.5\cos36.87^\circ}{1.2-0.5} \\ &= \frac{1.4850 - 0.7937 - 0.4000}{0.7} \\ &= 0.4161 \\ \delta_{cr} &= 65.41^\circ \end{aligned}
 Pe
 1.5 |     ___ I (pre)
 1.2 |   /  _ \__ III (post)
 0.9 |--*--|----\--------- Pm
 0.5 | / A1| A2  \  II (fault)
     +--d0-dcr----dmax---- delta

Answer: Critical clearing angle δcr≈65.4∘\delta_{cr} \approx 65.4^\circ.

✓ Answer checked by Claude Sonnet 5.5

All Power System Analysis II chapter 6 questions →