Short answer

Using equal area criterion with zero electrical power during the fault, the critical clearing angle is 59.23° and the critical clearing time is 0.187 s (about 9.3cycles at 50 Hz).

Calculate the critical clearing time and critical angle if the fault is at point P for the network having inertia 5 MJ/MVA shown below. The machine is delivering 1.0 pu and both the terminal voltage and the infinite bus voltage are 1.0 pu. [Figure: generator G (j0.2) - transformer j0.1 - bus with V1 = 1.0; two parallel lines each j0.4 with breakers at both ends to the bus V2 and the infinite bus; fault P at the sending end of one line, which is opened to clear the fault]

Data: Xd′=0.2X_d' = 0.2, XT=0.1X_T = 0.1, two lines of 0.40.4 pu each, H=5H = 5 MJ/MVA, f=50f = 50 Hz (assumed), Pm=1.0P_m = 1.0 pu. V1=1.0V_1 = 1.0 pu at the bus marked in the figure (the HV bus after the transformer), and V2=1.0V_2 = 1.0 pu at the infinite bus.

Assumptions: P is at the sending end of one line, and the fault is cleared by opening that line.

Step 1: Pre-fault operating point

Reactance from V1V_1 to the infinite bus: 0.4/2=0.20.4/2 = 0.2 pu.

sin⁡θ=PXV1V2=1×0.21=0.2  ⇒  θ=11.54∘I=1∠11.54∘−1∠0∘j0.2=1.0+j0.1010 puE′=V1+j(0.2+0.1)I=(0.9798+j0.2)+j0.3(1.0+j0.1010)=0.9495+j0.5=1.0731∠27.77∘\begin{aligned} \sin\theta &= \frac{P X}{V_1V_2} = \frac{1\times 0.2}{1} = 0.2 \;\Rightarrow\; \theta = 11.54^\circ \\ I &= \frac{1\angle11.54^\circ - 1\angle0^\circ}{j0.2} = 1.0 + j0.1010\ \text{pu} \\ E' &= V_1 + j(0.2+0.1)I = (0.9798 + j0.2) + j0.3(1.0 + j0.1010) \\ &= 0.9495 + j0.5 = 1.0731\angle 27.77^\circ \end{aligned}

So δ0=27.77∘=0.4847\delta_0 = 27.77^\circ = 0.4847 rad.

Step 2: Power-angle curves

ConditionXX (pu)PmaxP_{max} (pu)
Pre-fault0.2+0.1+0.2=0.50.2+0.1+0.2 = 0.51.0731/0.5=2.1461.0731/0.5 = 2.146
During fault (P at bus)—00
Post-fault (one line)0.2+0.1+0.4=0.70.2+0.1+0.4 = 0.71.0731/0.7=1.5331.0731/0.7 = 1.533
δmax=180∘−sin⁡−111.533=139.28∘=2.4310 rad\delta_{max} = 180^\circ - \sin^{-1}\frac{1}{1.533} = 139.28^\circ = 2.4310\ \text{rad}

Step 3: Critical clearing angle

cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmaxPmax3=1(2.4310−0.4847)+1.533cos⁡139.28∘1.533=0.5116δcr=59.23∘=1.0337 rad\begin{aligned} \cos\delta_{cr} &= \frac{P_m(\delta_{max}-\delta_0) + P_{max3}\cos\delta_{max}}{P_{max3}} \\ &= \frac{1(2.4310-0.4847) + 1.533\cos139.28^\circ}{1.533} \\ &= 0.5116 \\ \delta_{cr} &= 59.23^\circ = 1.0337\ \text{rad} \end{aligned}

Step 4: Critical clearing time

With Pe=0P_e = 0 during the fault:

tcr=2H(δcr−δ0)πfPm=2×5×(1.0337−0.4847)π×50×1=0.187 s\begin{aligned} t_{cr} &= \sqrt{\frac{2H(\delta_{cr}-\delta_0)}{\pi f P_m}} \\ &= \sqrt{\frac{2\times5\times(1.0337-0.4847)}{\pi\times50\times1}} \\ &= 0.187\ \text{s} \end{aligned}

Answer: δcr≈59.2∘\delta_{cr} \approx 59.2^\circ, tcr≈0.187t_{cr} \approx 0.187 s (about 9.3 cycles).

If "terminal voltage" is instead taken at the generator terminals (before the transformer), then E′=1.05∠28.44∘E' = 1.05\angle28.44^\circ, Pmax1=2.1P_{max1} = 2.1, Pmax3=1.5P_{max3} = 1.5, which gives δcr=57.9∘\delta_{cr} = 57.9^\circ and tcr=0.181t_{cr} = 0.181 s.