- 2076 Asoj · 8 marks
Critical clearing time and angle, fault at P
Short answer
Using equal area criterion with zero electrical power during the fault, the critical clearing angle is 59.23° and the critical clearing time is 0.187 s (about 9.3cycles at 50 Hz).
Calculate the critical clearing time and critical angle if the fault is at point P for the network having inertia 5 MJ/MVA shown below. The machine is delivering 1.0 pu and both the terminal voltage and the infinite bus voltage are 1.0 pu. [Figure: generator G (j0.2) - transformer j0.1 - bus with V1 = 1.0; two parallel lines each j0.4 with breakers at both ends to the bus V2 and the infinite bus; fault P at the sending end of one line, which is opened to clear the fault]
Data: , , two lines of pu each, MJ/MVA, Hz (assumed), pu. pu at the bus marked in the figure (the HV bus after the transformer), and pu at the infinite bus.
Assumptions: P is at the sending end of one line, and the fault is cleared by opening that line.
Step 1: Pre-fault operating point
Reactance from to the infinite bus: pu.
So rad.
Step 2: Power-angle curves
| Condition | (pu) | (pu) |
|---|---|---|
| Pre-fault | ||
| During fault (P at bus) | — | |
| Post-fault (one line) |
Step 3: Critical clearing angle
Step 4: Critical clearing time
With during the fault:
Answer: , s (about 9.3 cycles).
If "terminal voltage" is instead taken at the generator terminals (before the transformer), then , , , which gives and s.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing, fault at infinite bus, H = 6 · Power System Analysis II, chapter 6
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- Critical clearing angle, Pmax 2, 0.5, 1.5 · Power System Analysis II, chapter 6
- Critical clearing angle and time, H = 2 · Power System Analysis II, chapter 6
- Generator on infinite bus with 15% excitation rise · Electric Machines II, chapter 1
- Fault level: four 25 MVA generators, bus reactor · Power Plant Equipment, chapter 4
- Power transfer and pf of motor on infinite bus · Electric Machines II, chapter 2