Why infinite bus frequency and voltage stay constant

Short answer

The voltage remains constant because the Thevenin impedance of a large grid is nearly zero, so load current changes cause negligible voltage drop. The frequency stays fixed because total inertia of all generators is so high that any load change causes only minuscule speed deviation.

Give reason in brief: the frequency and voltage of an infinite bus remain constant even after variation in load.

An infinite bus is a bus of a very large system (ideally zero impedance and infinite inertia), so a load change at one point is negligible compared with its capacity.

  • Voltage constant: Bus voltage V=Eth−IZthV = E_{th} - IZ_{th}. For a huge interconnected system, Zth≈0Z_{th}\approx0 (very high fault level), so a change in load current produces almost no voltage drop; also many generators with AVRs share the reactive demand.
  • Frequency constant: Frequency changes when the power balance changes, at a rate set by system inertia (df/dt∝ΔP/Hdf/dt \propto \Delta P/H). The total inertia of all machines is extremely large, and many governors share any load change, so Δf≈0\Delta f \approx 0.

Hence a load change that is tiny relative to the total generation leaves the voltage and frequency practically unchanged.