Critical clearing angle, breakers 1 and 2
Short answer
Pre-fault: X1=0.522 pu, Pmax1=2.298 pu, δ0=25.8°. During fault at receiving bus: Pmax2=0. Post-fault (j0.4 line removed): X3=0.8 pu, Pmax3=1.5 pu, δmax=138.2°. Using equal area criterion with Pmax2=0: cosδcr = [Pm(δmax-δ0) + Pmax3cosδmax]/Pmax3 = 0.5624. Critical clearing angle δcr = 55.8°.
A three phase fault is applied at the point P as shown in figure below. Find the critical clearing angle for clearing the fault with simultaneous opening of the breakers 1 and 2. The reactance values of various components are indicated in the diagram. The generator is delivering 1.0 pu power at the instant preceding the fault. [Figure: generator |E| = 1.2 pu, reactance j0.25 to the sending bus; two parallel lines j0.5 and j0.4 between the sending and receiving buses; the j0.4 line has breakers 1 (sending end) and 2 (receiving end) and the fault P is on it near breaker 2; reactance j0.05 from the receiving bus to the infinite bus |V| = 1∠0]
Data: pu, pu, pu. Generator reactance j0.25, parallel lines j0.5 and j0.4, j0.05 to the infinite bus. The fault P is on the j0.4 line next to breaker 2, i.e. practically at the receiving-end bus.
1. Pre-fault (both lines in)
2. During fault
The fault at P is at the receiving bus, which is the only path from the generator to the infinite bus. That bus is at zero voltage, so no power reaches the infinite bus:
3. Post-fault (j0.4 line removed by breakers 1 and 2)
4. Equal area criterion
Pe
^ post-fault 1.5 sin(d)
| .--''''--.
| .' A2 '.
1|....+---+---------------+.... Pm = 1.0
| |A1 | \
| | | \
+----+---+------------------+--> d
d0 dc dmax
During fault Pe = 0, so A1 = Pm(dc - d0)
Accelerating area must equal decelerating area . This gives
Substituting ():
Answer: critical clearing angle (initial angle 25.8°). Breakers 1 and 2 must open before the rotor swings beyond 55.8°, otherwise the machine loses synchronism.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Critical clearing angle, Pm = 1.2 pu · Power System Analysis II, chapter 6
- Critical clearing time and angle, fault at P · Power System Analysis II, chapter 6
- Critical clearing angle/time, fault at infinite bus · Power System Analysis II, chapter 6
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6
- Critical clearing time, H = 8 MJ/MVA · Power System Analysis II, chapter 6
- Critical clearing angle and time, H = 2 · Power System Analysis II, chapter 6
- Reactance diagram: 90 MVA generator (25%), two motors · Power System Analysis I, chapter 3 · asked 2×
- Reactance diagram: 300 MVA, 20 kV generator, two motors · Power System Analysis I, chapter 3
- Reactance diagram: 30 MVA, 6.6 kV base, three lines · Power System Analysis I, chapter 3
- Reactance diagram: 90 MVA generator (15%), two motors · Power System Analysis I, chapter 3 · asked 2×