Critical clearing angle, breakers 1 and 2

Short answer

Pre-fault: X1=0.522 pu, Pmax1=2.298 pu, δ0=25.8°. During fault at receiving bus: Pmax2=0. Post-fault (j0.4 line removed): X3=0.8 pu, Pmax3=1.5 pu, δmax=138.2°. Using equal area criterion with Pmax2=0: cosδcr = [Pm(δmax-δ0) + Pmax3cosδmax]/Pmax3 = 0.5624. Critical clearing angle δcr = 55.8°.

A three phase fault is applied at the point P as shown in figure below. Find the critical clearing angle for clearing the fault with simultaneous opening of the breakers 1 and 2. The reactance values of various components are indicated in the diagram. The generator is delivering 1.0 pu power at the instant preceding the fault. [Figure: generator |E| = 1.2 pu, reactance j0.25 to the sending bus; two parallel lines j0.5 and j0.4 between the sending and receiving buses; the j0.4 line has breakers 1 (sending end) and 2 (receiving end) and the fault P is on it near breaker 2; reactance j0.05 from the receiving bus to the infinite bus |V| = 1∠0]

Data: ∣E∣=1.2|E| = 1.2 pu, ∣V∣=1.0|V| = 1.0 pu, Pm=1.0P_m = 1.0 pu. Generator reactance j0.25, parallel lines j0.5 and j0.4, j0.05 to the infinite bus. The fault P is on the j0.4 line next to breaker 2, i.e. practically at the receiving-end bus.

1. Pre-fault (both lines in)

X1=0.25+(0.5∥0.4)+0.05=0.25+0.2222+0.05=0.5222 puPmax1=EVX1=1.2×10.5222=2.298 puδ0=sin⁡−1PmPmax1=sin⁡−112.298=25.80∘=0.4502 rad\begin{aligned} X_1 &= 0.25 + (0.5\|0.4) + 0.05 = 0.25 + 0.2222 + 0.05 = 0.5222\ \text{pu} \\ P_{max1} &= \frac{EV}{X_1} = \frac{1.2 \times 1}{0.5222} = 2.298\ \text{pu} \\ \delta_0 &= \sin^{-1}\frac{P_m}{P_{max1}} = \sin^{-1}\frac{1}{2.298} = 25.80^\circ = 0.4502\ \text{rad} \end{aligned}

2. During fault

The fault at P is at the receiving bus, which is the only path from the generator to the infinite bus. That bus is at zero voltage, so no power reaches the infinite bus:

Pmax2=0P_{max2} = 0

3. Post-fault (j0.4 line removed by breakers 1 and 2)

X3=0.25+0.5+0.05=0.80 puPmax3=1.2×10.8=1.5 puδmax=180∘−sin⁡−111.5=180∘−41.81∘=138.19∘=2.4119 rad\begin{aligned} X_3 &= 0.25 + 0.5 + 0.05 = 0.80\ \text{pu} \\ P_{max3} &= \frac{1.2 \times 1}{0.8} = 1.5\ \text{pu} \\ \delta_{max} &= 180^\circ - \sin^{-1}\frac{1}{1.5} = 180^\circ - 41.81^\circ = 138.19^\circ = 2.4119\ \text{rad} \end{aligned}

4. Equal area criterion

 Pe
  ^           post-fault 1.5 sin(d)
  |            .--''''--.
  |         .'    A2      '.
 1|....+---+---------------+.... Pm = 1.0
  |    |A1 |                \
  |    |   |                 \
  +----+---+------------------+--> d
      d0   dc               dmax
 During fault Pe = 0, so A1 = Pm(dc - d0)

Accelerating area A1=Pm(δc−δ0)A_1 = P_m(\delta_c - \delta_0) must equal decelerating area A2=∫δcδmax(Pmax3sin⁡δ−Pm) dδA_2 = \int_{\delta_c}^{\delta_{max}}(P_{max3}\sin\delta - P_m)\,d\delta. This gives

cos⁡δcr=Pm(δmax−δ0)+Pmax3cos⁡δmax−Pmax2cos⁡δ0Pmax3−Pmax2\cos\delta_{cr} = \frac{P_m(\delta_{max} - \delta_0) + P_{max3}\cos\delta_{max} - P_{max2}\cos\delta_0}{P_{max3} - P_{max2}}

Substituting (Pmax2=0P_{max2} = 0):

cos⁡δcr=1.0 (2.4119−0.4502)+1.5cos⁡138.19∘1.5=1.9617+1.5(−0.7454)1.5=1.9617−1.11801.5=0.5624δcr=cos⁡−1(0.5624)=55.78∘\begin{aligned} \cos\delta_{cr} &= \frac{1.0\,(2.4119 - 0.4502) + 1.5\cos138.19^\circ}{1.5} \\ &= \frac{1.9617 + 1.5(-0.7454)}{1.5} = \frac{1.9617 - 1.1180}{1.5} = 0.5624 \\ \delta_{cr} &= \cos^{-1}(0.5624) = 55.78^\circ \end{aligned}

Answer: critical clearing angle δcr≈55.8∘\delta_{cr} \approx 55.8^\circ (initial angle 25.8°). Breakers 1 and 2 must open before the rotor swings beyond 55.8°, otherwise the machine loses synchronism.