280 km, 60 Hz line: nominal-π vs long line

Short answer

Per-phase: V_R=127.02 kV, I_R=262.4 A at 0.8 lag. Nominal-π: V_S=251.03 kV, I_S=201.8 A, p.f. 0.9715 lag, P_S=85.24 MW. Exact long-line: V_S=250.23 kV, I_S=202.1 A, p.f. 0.9729 lag, P_S=85.21 MW. The difference is <0.3%, confirming nominal-π is acceptable for 280 km.

A 280 km long transmission line on a 60 Hz system has line impedance of (33 + j104) Ω, a total shunt admittance of 10⁻³ mho. The receiving end feeds a load of 80 MW at 220 kV at 0.8 p.f. lagging. Find the sending-end voltage, current, power and power factor using (i) nominal pi method (ii) long line, and comment on the results.

Given: Z=33+j104 ΩZ = 33 + j104\ \Omega, Y=j10−3Y = j10^{-3} S (totals, so frequency is not needed), load 80 MW at 220 kV, 0.8 p.f. lagging. Per-phase values are used.

VR=2203=127.02∠0∘ kVIR=80×1063×220×103×0.8=262.4∠−36.87∘=209.95−j157.46 A\begin{aligned} V_R &= \frac{220}{\sqrt3} = 127.02\angle 0^\circ\ \text{kV} \\ I_R &= \frac{80\times10^6}{\sqrt3\times220\times10^3\times0.8} = 262.4\angle -36.87^\circ = 209.95 - j157.46\ \text{A} \end{aligned}

(i) Nominal-Π method

ZY=(33+j104)(j10−3)=−0.104+j0.033A=D=1+ZY2=0.948+j0.0165=0.9481∠0.997∘B=Z=109.1∠72.40∘ ΩC=Y(1+ZY4)=9.74×10−4∠90.49∘ S\begin{aligned} ZY &= (33 + j104)(j10^{-3}) = -0.104 + j0.033 \\ A = D &= 1 + \frac{ZY}{2} = 0.948 + j0.0165 = 0.9481\angle 0.997^\circ \\ B &= Z = 109.1\angle 72.40^\circ\ \Omega \\ C &= Y\left(1 + \frac{ZY}{4}\right) = 9.74\times10^{-4}\angle 90.49^\circ\ \text{S} \end{aligned} VS=AVR+BIR=(120,410+j2096)+(23,304+j16,638)=143,720+j18,734=144.93∠7.43∘ kV/phaseVS(L)=3×144.93=251.03 kVIS=CVR+DIR=200.58−j22.09=201.8∠−6.29∘ A\begin{aligned} V_S &= AV_R + BI_R = (120{,}410 + j2096) + (23{,}304 + j16{,}638) \\ &= 143{,}720 + j18{,}734 = 144.93\angle 7.43^\circ\ \text{kV/phase} \\ V_{S(L)} &= \sqrt3 \times 144.93 = 251.03\ \text{kV} \\ I_S &= CV_R + DI_R = 200.58 - j22.09 = 201.8\angle -6.29^\circ\ \text{A} \end{aligned}

p.f. =cos⁡(7.43∘+6.29∘)=cos⁡13.71∘=0.9715= \cos(7.43^\circ + 6.29^\circ) = \cos 13.71^\circ = 0.9715 lagging

PS=3VSIScos⁡ϕS=85.24P_S = 3V_SI_S\cos\phi_S = 85.24 MW (and QS=20.80Q_S = 20.80 Mvar)

(ii) Long-line (exact) method

γl=ZY=0.3303∠81.20∘=0.05055+j0.3264Zc=Z/Y=330.3∠−8.80∘ ΩA=D=cosh⁡γl=0.9484+j0.0162=0.9485∠0.98∘B=Zcsinh⁡γl=107.2∠72.71∘ ΩC=sinh⁡γlZc=9.828×10−4∠90.32∘ S\begin{aligned} \gamma l &= \sqrt{ZY} = 0.3303\angle 81.20^\circ = 0.05055 + j0.3264 \\ Z_c &= \sqrt{Z/Y} = 330.3\angle -8.80^\circ\ \Omega \\ A = D &= \cosh\gamma l = 0.9484 + j0.0162 = 0.9485\angle 0.98^\circ \\ B &= Z_c\sinh\gamma l = 107.2\angle 72.71^\circ\ \Omega \\ C &= \frac{\sinh\gamma l}{Z_c} = 9.828\times10^{-4}\angle 90.32^\circ\ \text{S} \end{aligned} VS=AVR+BIR=143,270+j18,538=144.46∠7.37∘ kV/phaseVS(L)=250.23 kVIS=CVR+DIR=200.98−j21.11=202.1∠−6.00∘ A\begin{aligned} V_S &= AV_R + BI_R = 143{,}270 + j18{,}538 = 144.46\angle 7.37^\circ\ \text{kV/phase} \\ V_{S(L)} &= 250.23\ \text{kV} \\ I_S &= CV_R + DI_R = 200.98 - j21.11 = 202.1\angle -6.00^\circ\ \text{A} \end{aligned}

p.f. =cos⁡(7.37∘+6.00∘)=0.9729= \cos(7.37^\circ + 6.00^\circ) = 0.9729 lagging, PS=85.21P_S = 85.21 MW (QS=20.25Q_S = 20.25 Mvar)

Results and comment

QuantityNominal-ΠLong line
VSV_S (line)251.03 kV250.23 kV
ISI_S201.8 A202.1 A
Sending p.f.0.9715 lag0.9729 lag
PSP_S85.24 MW85.21 MW
Efficiency93.86 %93.89 %
  • The two methods differ by only about 0.3 % in voltage, so for 280 km the nominal-Π model is reasonably accurate.
  • The long-line method is exact. The error of the Π model grows with length, so the exact model should be used for lines well above 250 km.
  • In both, IS<IRI_S < I_R because the line's charging current partly cancels the lagging load current.

Answer: Nominal-Π: VS=251.03V_S = 251.03 kV, IS=201.8I_S = 201.8 A, p.f. 0.9715 lag, PS=85.24P_S = 85.24 MW. Long line: VS=250.23V_S = 250.23 kV, IS=202.1I_S = 202.1 A, p.f. 0.9729 lag, PS=85.21P_S = 85.21 MW.