- Asked 2/23
- 2081 Chaitra (new course) · 4+4 marks
280 km, 60 Hz line: nominal-π vs long line
Short answer
Per-phase: V_R=127.02 kV, I_R=262.4 A at 0.8 lag. Nominal-π: V_S=251.03 kV, I_S=201.8 A, p.f. 0.9715 lag, P_S=85.24 MW. Exact long-line: V_S=250.23 kV, I_S=202.1 A, p.f. 0.9729 lag, P_S=85.21 MW. The difference is <0.3%, confirming nominal-π is acceptable for 280 km.
A 280 km long transmission line on a 60 Hz system has line impedance of (33 + j104) Ω, a total shunt admittance of 10⁻³ mho. The receiving end feeds a load of 80 MW at 220 kV at 0.8 p.f. lagging. Find the sending-end voltage, current, power and power factor using (i) nominal pi method (ii) long line, and comment on the results.
Given: , S (totals, so frequency is not needed), load 80 MW at 220 kV, 0.8 p.f. lagging. Per-phase values are used.
(i) Nominal-Π method
p.f. lagging
MW (and Mvar)
(ii) Long-line (exact) method
p.f. lagging, MW ( Mvar)
Results and comment
| Quantity | Nominal-Π | Long line |
|---|---|---|
| (line) | 251.03 kV | 250.23 kV |
| 201.8 A | 202.1 A | |
| Sending p.f. | 0.9715 lag | 0.9729 lag |
| 85.24 MW | 85.21 MW | |
| Efficiency | 93.86 % | 93.89 % |
- The two methods differ by only about 0.3 % in voltage, so for 280 km the nominal-Π model is reasonably accurate.
- The long-line method is exact. The error of the Π model grows with length, so the exact model should be used for lines well above 250 km.
- In both, because the line's charging current partly cancels the lagging load current.
Answer: Nominal-Π: kV, A, p.f. 0.9715 lag, MW. Long line: kV, A, p.f. 0.9729 lag, MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 300 km line: short line vs nominal-π · Power System Analysis I, chapter 5 · asked 2×
- 8 km line receiving 15000 kVA at 33 kV · Power System Analysis I, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- 150 km line with mid-point shunt capacitor · Power System Analysis I, chapter 6
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3