- 2070 Bhadra · 6 marks
150 km line with mid-point shunt capacitor
Short answer
With a shunt capacitor of susceptance 4×10⁻⁶ S at the midpoint, the transmission efficiency is approximately 96.7%.
A 150 km long, 50 Hz, 132 kV, 3-phase overhead line with series impedance of 0.1 + j0.3 Ω/m and shunt admittance of 3 × 10⁻⁶∠90° S/km is feeding a load of 35 MW at 0.9 p.f. lagging. Determine the transmission line efficiency when a shunt capacitor of susceptance 4 × 10⁻⁶∠90° S is connected at the middle of the line.
Assumptions: the series impedance is taken as /km (Ω/m is a misprint). The load is at 132 kV. The line is modelled as two 75 km nominal-π sections with the capacitor at the junction.
Section constants (75 km each)
At the middle bus, the two half-section admittances and the capacitor add: S.
Vs Zh Vm Zh Vr
o---/\/\/---+-----+-----+---/\/\/---o
| | | | |
Yh/2 Yh/2 Ysh Yh/2 Yh/2
| | | | |
o-----------+-----+-----+-----------o
Receiving-end section
Middle bus and sending section
Sending-end line voltage kV.
Efficiency
(Check: MW loss.)
A S capacitor supplies only about MVAr, so it hardly changes the result (without it, = 96.68 %).
Answer: Transmission efficiency ≈ 96.7 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 150 km line by T-model, 60 MW · Power System Analysis I, chapter 5
- Conductor selection, 100 MW 70 km 132 kV · Transmission and Distribution System Design, chapter 4
- Arc suppression coil for 66 kV 90 km line · Switchgear and Protection, chapter 5 · asked 6×
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×