300 km line: short line vs nominal-π
Short answer
Short line: V_S=251.33 kV, I_S=164.0 A, pf=0.7455 lag, P_S=53.23 MW. Nominal-π: V_S=238.07 kV, I_S=128.1 A, pf=0.9881 lead, P_S=52.21 MW.
A 50 Hz transmission line 300 km long has a total series impedance of 40 + j125 ohms and a total shunt admittance of 10⁻³ mho. The receiving-end load is 50 MW at 220 kV with 0.8 lagging power factor. Find the sending-end voltage, current, power and power factor using: (i) short line approximation (ii) nominal-π method.
Given: , S (totals), load 50 MW at 220 kV, 0.8 p.f. lagging. Per-phase working.
MW, Mvar.
(i) Short-line approximation (, , )
p.f. lagging
(ii) Nominal-Π method
p.f. leading (current leads voltage)
Comparison
| Quantity | Short line | Nominal-Π |
|---|---|---|
| (line) | 251.33 kV | 238.07 kV |
| 164.0 A | 128.1 A | |
| Sending p.f. | 0.7455 lag | 0.9881 lead |
| 53.23 MW | 52.21 MW | |
| Efficiency | 93.94 % | 95.76 % |
The short-line model ignores about 123 A of charging current, so for a 300 km line it badly overestimates and . The nominal-Π (or better, the exact long-line) model must be used.
Answer: (i) kV, A, p.f. 0.7455 lag, MW. (ii) kV, A, p.f. 0.9881 lead, MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- Nominal-T 100 km line, 20 MW at 110 kV · Power System Analysis I, chapter 5
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- Equivalent-T of 300 km long line · Power System Analysis I, chapter 5
- 150 km line with mid-point shunt capacitor · Power System Analysis I, chapter 6
- 450 km 400 kV line, 420 MW, 0.9 pf · Power System Analysis I, chapter 5
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- Load sharing: 600 and 300 MW at 49 Hz · Power Plant Equipment, chapter 2 · asked 4×
- Mid-line reactor for Vr = Vs at no load · High Voltage Engineering, chapter 3
- Load sharing: 600 and 300 MW, 51 Hz no-load · Power Plant Equipment, chapter 2