Load sharing: 600 and 300 MW at 49 Hz
Short answer
At 50 Hz, G1 output is 0 MW and G2 output is 150 MW. Total system load is 150 MW.
Two generators of 600MW, 2% and 300 MW, 4% are supplying to a common load. When each generator is fully loaded, they operate at common frequency of 49 Hz. Calculate the system load shared by each unit when frequency increased to 50Hz.
Both units are fully loaded at 49 Hz. When frequency rises to 50 Hz, each sheds load equal to its stiffness times the frequency rise ( Hz).
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
| Unit | At 49 Hz (MW) | Change (MW) | At 50 Hz (MW) |
|---|---|---|---|
| G1 (600 MW, 2 %) | 600 | −600 | 0 |
| G2 (300 MW, 4 %) | 300 | −150 | 150 |
| Total | 900 | −750 | 150 |
Answer: At 50 Hz, G1 = 0 MW (its no-load frequency is Hz) and G2 = 150 MW; the system load is 150 MW.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 1000 MW and 500 MW units · Power Plant Equipment, chapter 2 · asked 4×
- Load sharing among three generators · Power Plant Equipment, chapter 2 · asked 3×
- Load reduction: 500 MW and 250 MW units · Power Plant Equipment, chapter 2 · asked 3×
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 and 300 MW, 51 Hz no-load · Power Plant Equipment, chapter 2
- Load decrease: 250 and 500 MW at 49 Hz · Power Plant Equipment, chapter 2
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 900 MW and 450 MW generators · Power Plant Equipment, chapter 2
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing between two stations in parallel · Electric Machines II, chapter 1