Load decrease: 250 and 500 MW at 49 Hz
Short answer
Each unit's stiffness is K = P_r/(R f0). G1: 250/(0.02×50)=250 MW/Hz; G2: 500/(0.04×50)=250 MW/Hz. With Δf=+1 Hz, each sheds 250 MW, so total load decrease is 500 MW; G1 falls to 0 MW, G2 to 250 MW.
Two generators of 250 MW and 500 MW capacities respectively are operating in parallel and supplying power to a common load. When each generator is fully loaded, they operate at a common frequency of 49 Hz. Their droop characteristics are 2% and 4% respectively based on their respective ratings. When the system load is decreased, the frequency increases to 50Hz. calculate the decrease in system load shared by each generator.
Both units are fully loaded at 49 Hz. As the load falls, frequency rises to 50 Hz and each unit sheds load equal to its stiffness times the rise ( Hz).
Method: a unit with droop (pu on its own rating ) and rated frequency changes its output by
where is its stiffness in MW/Hz. All units run at the same frequency, so .
| Generator | At 49 Hz (MW) | Decrease (MW) | At 50 Hz (MW) |
|---|---|---|---|
| G1 (250 MW, 2 %) | 250 | 250 | 0 |
| G2 (500 MW, 4 %) | 500 | 250 | 250 |
| Total | 750 | 500 | 250 |
Answer: The system load decreases by 500 MW, shared equally: 250 MW by G1 (which falls to no load) and 250 MW by G2 (which now supplies 250 MW).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 4%/3% droop · Power Plant Equipment, chapter 2
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Droop for capacity sharing: 500 and 250 MW · Power Plant Equipment, chapter 2
- Load sharing: 250 MW and 500 MW, 20%/10% droop · Power Plant Equipment, chapter 2 · asked 2×
- Droop for capacity sharing: 250 and 500 MW · Power Plant Equipment, chapter 2