Droop for capacity sharing: 500 and 250 MW
Short answer
For capacity-proportional sharing, both units must have the same per-unit droop. Therefore the 250 MW unit must have a droop of 5% on its own rating, same as the 500 MW unit.
Two generating units of 500MW and 250 MW capacities respectively are operating in parallel and supplying power to a common load. When each generator is half loaded, they operate at a common frequency of 50 Hz. If the droop regulation of 500MW generating set is 5% based on its rating, what must be the droop regulation of 250 MW generating unit based on its own rating so that they share the change in load according to their capacities.
For two units to share any change in load according to their capacities, each must change by the same fraction of its rating for the same frequency change.
From the droop definition, for a common :
Sharing by capacity requires
So .
Check with numbers: for, say, a 75 MW increase,
Ratio , i.e. in proportion to capacity ✓.
Answer: The 250 MW unit must have a droop of 5 % on its own rating (the same per-unit droop as the 500 MW unit).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 4%/3% droop · Power Plant Equipment, chapter 2
- Droop for capacity sharing: 250 and 500 MW · Power Plant Equipment, chapter 2
- Load sharing: 250 MW and 500 MW, 20%/10% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing between two stations in parallel · Electric Machines II, chapter 1