Load sharing: 250 MW and 500 MW, 20%/10% droop
Short answer
Stiffnesses: K1=25 MW/Hz, K2=100 MW/Hz. With a 60 MW load increase, frequency falls by 0.48 Hz to 49.52 Hz; unit loads become 137 MW and 298 MW.
Two generating units rated as 250 MW and 500 MW have speed droop regulation of 20% and 10% respectively based on their rating. They are operated in parallel and each is half loaded at a common frequency of 50 Hz. If the load is increased by 60 MW, calculate: i) New frequency at which operates ii) New loading of each generating units
When load rises, both units move down their droop lines to a common lower frequency; each picks up load in proportion to its stiffness .
Method: with droop (pu, on its own rating ) and rated frequency , the droop line of each unit gives
where is the stiffness of the unit in MW/Hz. For the units together, .
Data: MW, ; MW, ; Hz. Initial loading: 125 MW and 250 MW. MW.
Stiffness of each unit:
i) New frequency
ii) New loading of each unit
Check: MW.
| Unit | Rating (MW) | Droop | Initial (MW) | Increase (MW) | New load (MW) |
|---|---|---|---|---|---|
| 1 | 250 | 20 % | 125 | 12 | 137 |
| 2 | 500 | 10 % | 250 | 48 | 298 |
Answer: New frequency = 49.52 Hz; unit 1 carries 137 MW and unit 2 carries 298 MW. The 500 MW unit, with the smaller droop (stiffer), takes 80 % of the increase.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Droop for capacity sharing: 500 and 250 MW · Power Plant Equipment, chapter 2
- Load sharing: 500 MW and 250 MW, 5%/6% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 250 MW and 500 MW, 4%/3% droop · Power Plant Equipment, chapter 2
- Droop for capacity sharing: 250 and 500 MW · Power Plant Equipment, chapter 2
- Load sharing: 250/500 MW, frequency falls to 49.5 Hz · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing: 600 MW and 300 MW, 7%/8% droop · Power Plant Equipment, chapter 2 · asked 2×
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- Load sharing of two transformers in parallel · Electrical Machines, chapter 2
- 20 kVA 250/2500 V tests, regulation, efficiency · Electrical Machines, chapter 2