Short answer

Stiffnesses: K1=25 MW/Hz, K2=100 MW/Hz. With a 60 MW load increase, frequency falls by 0.48 Hz to 49.52 Hz; unit loads become 137 MW and 298 MW.

Two generating units rated as 250 MW and 500 MW have speed droop regulation of 20% and 10% respectively based on their rating. They are operated in parallel and each is half loaded at a common frequency of 50 Hz. If the load is increased by 60 MW, calculate: i) New frequency at which operates ii) New loading of each generating units

When load rises, both units move down their droop lines to a common lower frequency; each picks up load in proportion to its stiffness Pr/RP_r/R.

Method: with droop RiR_i (pu, on its own rating PriP_{ri}) and rated frequency f0f_0, the droop line of each unit gives

ΔPi=−PriRi f0 Δf=−Ki Δf\Delta P_i = -\frac{P_{ri}}{R_i\, f_0}\,\Delta f = -K_i\,\Delta f

where Ki=Pri/(Rif0)K_i = P_{ri}/(R_i f_0) is the stiffness of the unit in MW/Hz. For the units together, ΔPL=−Δf ∑Ki\Delta P_L = -\Delta f\,\sum K_i.

Data: Pr1=250P_{r1} = 250 MW, R1=0.20R_1 = 0.20; Pr2=500P_{r2} = 500 MW, R2=0.10R_2 = 0.10; f0=50f_0 = 50 Hz. Initial loading: 125 MW and 250 MW. ΔPL=+60\Delta P_L = +60 MW.

Stiffness of each unit:

K1=2500.20×50=25 MW/HzK2=5000.10×50=100 MW/HzK1+K2=125 MW/Hz\begin{aligned} K_1 &= \frac{250}{0.20 \times 50} = 25\ \text{MW/Hz} \\ K_2 &= \frac{500}{0.10 \times 50} = 100\ \text{MW/Hz} \\ K_1 + K_2 &= 125\ \text{MW/Hz} \end{aligned}

i) New frequency

Δf=−ΔPLK1+K2=−60125=−0.48 Hzfnew=50−0.48=49.52 Hz\begin{aligned} \Delta f &= -\frac{\Delta P_L}{K_1 + K_2} = -\frac{60}{125} = -0.48\ \text{Hz} \\ f_{new} &= 50 - 0.48 = 49.52\ \text{Hz} \end{aligned}

ii) New loading of each unit

ΔP1=K1×0.48=25×0.48=12 MWΔP2=K2×0.48=100×0.48=48 MW\begin{aligned} \Delta P_1 &= K_1 \times 0.48 = 25 \times 0.48 = 12\ \text{MW} \\ \Delta P_2 &= K_2 \times 0.48 = 100 \times 0.48 = 48\ \text{MW} \end{aligned}

Check: 12+48=6012 + 48 = 60 MW.

UnitRating (MW)DroopInitial (MW)Increase (MW)New load (MW)
125020 %12512137
250010 %25048298

Answer: New frequency = 49.52 Hz; unit 1 carries 137 MW and unit 2 carries 298 MW. The 500 MW unit, with the smaller droop (stiffer), takes 80 % of the increase.