- 2067 Mangsir (old course) · 8 marks
Load sharing of two transformers in parallel
Short answer
Total kVA = 100 kW / 0.8 = 125 kVA. Load shares inversely with impedances ZA=0.5+j3 Ω and ZB=0.6+j10 Ω. Transformer A supplies 95.98 kVA (78.17 kW, pf 0.814 lag); transformer B supplies 29.14 kVA (21.83 kW, pf 0.749 lag).
Two 1-phase transformers with equal number of turns have impedance of and with respect to the secondary. If they operate in parallel, determine how they will share total load of 100 kW at pf 0.8 lagging.
Two transformers with equal turns ratio have the same secondary voltage, and they share the load current in inverse proportion to their impedances.
Given: , (referred to secondary), total load kW at 0.8 pf lagging.
Total load
Current division. Let the total current be with as reference. For parallel branches:
Load shared (kVA = fraction of 125 kVA, since is common):
Check: kW.
| Transformer | kVA | kW | Power factor |
|---|---|---|---|
| A | 95.98 | 78.17 | 0.814 lag |
| B | 29.14 | 21.83 | 0.749 lag |
Answer: A supplies about 78.2 kW (96.0 kVA) and B about 21.8 kW (29.1 kVA). The transformer of lower impedance (A) carries the greater share.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2
- Load sharing of 50 kVA and 25 kVA transformers in parallel · Electrical Machines I, chapter 2
- Secondary voltage, regulation, pf for max regulation · Electrical Machines, chapter 2
- LV voltage of Δ–Y bank of 100 kVA transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines, chapter 2
- Load sharing between two stations in parallel · Electric Machines II, chapter 1
- Reactance diagram: 100 MVA base, two parallel paths · Power System Analysis I, chapter 3
- Optimum pf under two-part tariff (200 kW) · Industrial Power Distribution and Illumination, chapter 10
- PF improvement of 490 kW load at 6.6 kV · Industrial Power Distribution and Illumination, chapter 10 · asked 2×