Parallel transformers and per-unit impedance load sharing
Short answer
Parallel operation requires same voltage ratio, polarity, per-unit impedance, and X/R ratio. Equal per-unit impedance on each transformer's own kVA base makes load share proportional to rating; otherwise the unit with smaller per-unit impedance overloads.
Mention the conditions for parallel operation of transformer. "In parallel operation of transformer if we want to share load according to their capacity we have to match the per unit impedance of transformer according to their base." Justify this statement with mathematical expression.
Conditions for parallel operation
- Same voltage ratio (same primary and secondary voltage ratings), otherwise a circulating current flows even at no load.
- Same polarity, otherwise a dead short circuit occurs through the secondaries.
- Same per-unit (percentage) impedance, so that load is shared in proportion to kVA ratings.
- Same X/R ratio, so that both operate at the same power factor as the load.
- For three-phase units: same phase sequence and same phase displacement (same vector group).
Conditions 1, 2 and 5 are essential; 3 and 4 are desirable for proper load sharing.
Justification: load sharing depends on per-unit impedance
Consider transformers A and B with equal voltage ratios in parallel, with equivalent impedances and (referred to secondary), supplying load current at voltage .
I_A Z_A
+---->----[====]---+
| | I
E + +---->---- load (V)
| I_B Z_B |
+---->----[====]---+
Both have the same EMF and same terminal voltage , so the impedance drops are equal:
With :
Multiplying by gives kVA shares:
So the current shared by each is inversely proportional to its ohmic impedance.
Now write each impedance in per unit on its own rating. With rated currents , :
Substitute and into :
and are the fractional loadings of A and B. For both to carry the same fraction of their rating (load shared in proportion to kVA capacity):
Hence the per-unit impedances, each on its own base, must be equal. If they are not, the transformer with the smaller per-unit impedance takes more than its share and may be overloaded while the other is under-used. If also is equal, the impedance angles match and both currents are in phase with the load current, so no transformer works at a worse pf.
Example: a 500 kVA unit with pu and a 250 kVA unit with pu share 600 kVA as 400 kVA and 200 kVA (both 80% loaded).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Load sharing of 50 kVA and 25 kVA transformers in parallel · Electrical Machines I, chapter 2
- Need and conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- Transformer no-load operation and ideal transformer properties · Electrical Machines I, chapter 2
- Transformer no-load and load operation, constant core flux · Electrical Machines I, chapter 2 · asked 5×
- Real transformer no-load operation and amp-turn balance · Electrical Machines I, chapter 2
- Load sharing of two transformers in parallel · Electrical Machines, chapter 2
- Conditions for parallel operation of transformers · Electrical Machines, chapter 2
- Per-unit transformer impedance same on both sides · Power System Analysis I, chapter 3 · asked 4×
- Load sharing between two stations in parallel · Electric Machines II, chapter 1