400 km line at UPF: Zc, propagation, regulation

Short answer

Characteristic impedance Z_c = 313.4∠−2.73° Ω, propagation constant γ = 1.073×10⁻³∠87.27° per km, phase constant β = 1.072×10⁻³ rad/km. Sending voltage computed via ABCD parameters gives voltage regulation = 9.61 %.

A 50 Hz, 400 km long, 400 kV, 3-phase overhead transmission line delivering a power of 400 MW at unity power factor has series resistance of 3.2 × 10⁻⁵ Ohm/m, inductance of 1.066 × 10⁻⁶ H/m and shunt capacitance of 1.09 × 10⁻¹¹ F/m per phase. Compute the characteristic impedance, propagation constant and phase shift constant, and voltage regulation of the line.

Given: 50 Hz, l=400l = 400 km, 400 kV, 400 MW at unity p.f.; r=0.032 Ωr = 0.032\ \Omega/km, L=1.066L = 1.066 mH/km, C=0.0109 μC = 0.0109\ \muF/km (converted from per-metre values). Receiving voltage 400 kV.

Step 1: Series impedance and shunt admittance per km

z=0.032+j(2π×50×1.066×10−3)=0.032+j0.3349=0.3364∠84.54∘ Ω/kmy=j2π×50×1.09×10−8=j3.424×10−6 S/km\begin{aligned} z &= 0.032 + j(2\pi\times50\times1.066\times10^{-3}) = 0.032 + j0.3349 = 0.3364\angle 84.54^\circ\ \Omega/\text{km} \\ y &= j2\pi\times50\times1.09\times10^{-8} = j3.424\times10^{-6}\ \text{S/km} \end{aligned}

Step 2: Characteristic impedance

Zc=zy=0.3364∠84.54∘3.424×10−6∠90∘=313.4∠−2.73∘ ΩZ_c = \sqrt{\frac{z}{y}} = \sqrt{\frac{0.3364\angle 84.54^\circ}{3.424\times10^{-6}\angle 90^\circ}} = 313.4\angle -2.73^\circ\ \Omega

Step 3: Propagation and phase-shift constants

γ=zy=1.073×10−3∠87.27∘=5.11×10−5+j1.0721×10−3 /kmβ=1.0721×10−3 rad/km,α=5.11×10−5 Np/kmγl=0.02044+j0.42884\begin{aligned} \gamma &= \sqrt{zy} = 1.073\times10^{-3}\angle 87.27^\circ = 5.11\times10^{-5} + j1.0721\times10^{-3}\ /\text{km} \\ \beta &= 1.0721\times10^{-3}\ \text{rad/km}, \quad \alpha = 5.11\times10^{-5}\ \text{Np/km} \\ \gamma l &= 0.02044 + j0.42884 \end{aligned}

Step 4: ABCD constants

A=cosh⁡γl=0.90964+j0.00850=0.9097∠0.54∘B=Zcsinh⁡γl=130.5∠84.71∘ Ω\begin{aligned} A &= \cosh\gamma l = 0.90964 + j0.00850 = 0.9097\angle 0.54^\circ \\ B &= Z_c\sinh\gamma l = 130.5\angle 84.71^\circ\ \Omega \end{aligned}

Step 5: Sending-end voltage

VR=230.94∠0∘ kV,IR=400×1063×400×103=577.35∠0∘ AVS=AVR+BIR=230.3∠19.53∘ kV/phase=398.83 kV (line)\begin{aligned} V_R &= 230.94\angle 0^\circ\ \text{kV}, \quad I_R = \frac{400\times10^6}{\sqrt3\times400\times10^3} = 577.35\angle 0^\circ\ \text{A} \\ V_S &= AV_R + BI_R = 230.3\angle 19.53^\circ\ \text{kV/phase} = 398.83\ \text{kV (line)} \end{aligned}

Step 6: Voltage regulation

VR(NL)=∣VS∣∣A∣=398.830.9097=438.43 kV%VR=438.43−400400×100=9.61 %\begin{aligned} V_{R(NL)} &= \frac{|V_S|}{|A|} = \frac{398.83}{0.9097} = 438.43\ \text{kV} \\ \%\text{VR} &= \frac{438.43 - 400}{400}\times100 = 9.61\ \% \end{aligned}

The load (400 MW) is below the SIL (4002/313.4≈511400^2/313.4 \approx 511 MW), so the line generates net reactive power and VSV_S is slightly below VRV_R at full load.

Answer: Zc=313.4∠−2.73∘ ΩZ_c = 313.4\angle -2.73^\circ\ \Omega, γ=1.073×10−3∠87.27∘\gamma = 1.073\times10^{-3}\angle 87.27^\circ per km, β=1.072×10−3\beta = 1.072\times10^{-3} rad/km, voltage regulation =9.61%= 9.61\%.