RRRV from short circuit test (132 kV)
Short answer
With sinφ=0.9165 and V_m=107.78 kV, the average RRRV is 5.69 kV/μs for a grounded fault and 8.53 kV/μs for an ungrounded fault because the first-pole-to-clear factor is 1.5.
In a short circuit test on a 132 kV three phase system, the breaker gave the following results: pf of the fault is 0.4, recovery voltage is 0.9 of full line value and the natural frequency is 16 kHz. Determine the rate of rise of restriking voltage in following cases: i) Assume that symmetrical fault is grounded. ii) Assume that symmetrical fault is not grounded.
The rate of rise of restriking voltage (RRRV) is the slope of the transient voltage across the CB contacts after current zero; it decides whether the arc re-ignites.
Method
- Peak phase voltage: V_m = √2 × V_L/√3.
- At current zero the instantaneous system voltage is V_m sin φ (fault current lags by φ, cos φ = fault p.f.).
- Active recovery voltage: V_r = k × sin φ × V_m, where k is the recovery voltage factor (0.9 of full line value).
- For an ungrounded symmetrical fault the first pole to clear sees 1.5 times this (first-pole-to-clear factor 1.5).
- Restriking voltage peak = 2 V_r, reached at t = 1/(2f_n).
- RRRV (average up to the peak, the usual textbook value) = 2V_r / t = 4 f_n V_r. The maximum instantaneous rate is ω_n V_r.
Data
V_L = 132 kV, cos φ = 0.4, k = 0.9, f_n = 16 kHz.
sin φ = √(1 − 0.4²) = 0.9165
V_m = √2 × 132/√3 = 107.78 kV
t = 1/(2 × 16000) = 31.25 μs
i) Fault grounded
V_r = 0.9 × 0.9165 × 107.78 = 88.90 kV
Peak = 2 × 88.90 = 177.80 kV
RRRV = 177.80 kV / 31.25 μs = 5.69 kV/μs
(max instantaneous = ω_n V_r
= 2π×16000×88.90 kV = 8.94 kV/μs)
ii) Fault not grounded (first-pole factor 1.5)
V_r = 1.5 × 88.90 = 133.35 kV
Peak = 2 × 133.35 = 266.71 kV
RRRV = 266.71 kV / 31.25 μs = 8.53 kV/μs
(max instantaneous = 13.41 kV/μs)
Answer: RRRV ≈ 5.69 kV/μs with a grounded fault and ≈ 8.53 kV/μs with an ungrounded fault (average up to the first peak).
An ungrounded fault therefore puts 50% more stress on the breaker.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- RRRV from short circuit test (220 kV) · Switchgear and Protection, chapter 6 · asked 2×
- Recovery, restriking voltage, RRRV and derivation · Switchgear and Protection, chapter 6
- Specifying breaker on 132/66 kV transformer · Switchgear and Protection, chapter 6
- Resistance switching numerical (132 kV, 350 Ω) · Switchgear and Protection, chapter 6 · asked 2×
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Current chopping overvoltage in 132 kV breaker · High Voltage Engineering, chapter 3
- Fault at receiving end of 132 kV lines · Power System Analysis II, chapter 3
- Nominal-T 100 km line, 50 MVA at 132 kV · Power System Analysis I, chapter 6