- 2071 Bhadra · 8 marks
Air clearances for 220 kV double circuit line
Short answer
Cross arm length 4.20 m, insulator string length 2.34 m (14 discs), vertical conductor separation 4.88 m, horizontal separation between circuits 9.89 m, and earth wire height above top conductor 8.57 m, based on 45° swing and 2.54 m minimum air clearance.
For a double circuit, 220 kV transmission line, find the following air clearance with justifications. i) Cross arm length ii) Insulator string length iii) Horizontal and vertical separation of conductor iv) Height of earth wire from top most conductor
Air clearances fix the size of the tower. They come from the minimum air clearance , the insulator string length , and the swing of the string.
Data and assumptions: maximum system voltage 245 kV (phase rms 141.45 kV); 254 × 146 mm disc insulators; maximum swing of the suspension string 45°; minimum air clearance 6.5 inch per 10 kV (phase rms) plus 8 inch safety, as given with IOE papers; tower body width at cross-arm level about 1.5 m.
Minimum air clearance (a)
Insulator string length (l)
- Number of discs: the standard 220 kV suspension string has 14 discs.
- Check against the withstand and flashover tables: the 1-min wet withstand of 395 kV and the impulse withstand of 900 kV each need 10 discs. Extra discs are added for switching surges, pollution and one defective disc, giving 13–14.
- Length:
Cross arm length (X)
The swung string must keep the conductor at least from the tower body:
measured from the tower face to the point of suspension.
Vertical separation (Y)
The conductor hanging under one cross arm must clear the cross arm below by :
Horizontal separation
In a double-circuit tower, each circuit is arranged vertically on one side of the tower. The horizontal distance between the conductors of the two circuits at the same level is:
Height of earth wire above the top conductor
Use one earth wire at the tower peak with a shielding angle of at most 30° to the outer top conductors. The horizontal offset is m, so
This is about 6.2 m above the top cross arm, since the conductor hangs 2.34 m below that cross arm.
E earth wire
/|\ 30 deg shielding
/ | \
*------o--+--o------* top arm, conductors
| | hang l below arm
*------o-----o------* Y = 4.88 m
| |
*------o-----o------*
X=4.2m w X=4.2m
| Item | Value |
|---|---|
| Minimum air clearance | 2.54 m |
| Insulator string length | 2.34 m (14 discs) |
| Cross arm length | 4.20 m |
| Vertical separation | 4.88 m |
| Horizontal separation (circuit to circuit) | 9.89 m |
| Earth wire above top conductor | 8.57 m |
Answer: cross arm about 4.2 m, string 2.34 m, vertical spacing about 4.9 m, horizontal spacing about 9.9 m, and earth wire about 8.6 m above the top conductor.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Tower dimensions for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×
- Air clearances for 220 kV single circuit line · Transmission and Distribution System Design, chapter 4
- Initial line design for 200 MW over 120 km · Transmission and Distribution System Design, chapter 2
- True/false: cross-arm length and string efficiency · High Voltage Engineering, chapter 5
All Transmission and Distribution System Design chapter 4 questions →